IL17569C
Page 5-58
FP-5000
Effective Date: 12/05
Page 5-58
For more information visit:
www.eatonelectrical.com
Effective Date: 12/05
Table 5.13 System Alarms
Breaker Alarm
Breaker Alarm Settings
Default Setting
# of Operation:
9999
Isum INTR Amp:
50,000
Table 5.14 Logging Settings
Current Demand
Current Demand Settings
Default Setting
Interval (m):
15
Power Demand
Power Demand Settings
Default Setting
Window:
Fixed
Interval (m):
15
Event Log Enable
Event Log Enable Settings
Default Setting
I Pickup:
Yes
Data Logger
Data Logger Settings
Default Setting
Mode:
Cont.
Trigger:
Auto
Interval (s):
900
Value 1:
Ia
Value 2:
Ib
Value 3:
Ic
Value 4:
Ix
Value 5:
Va
Value 6:
Vb
Value 7:
Vc
Value 8:
Vx
Waveform Capture
Waveform Capture Settings
Default Setting
Records:
16x16
PreTrigger:
2
OSC Trigger TRIP2:
Overwrite
OSC Trigger dV/dI:
Disable
OSC Trigger Logic LG6:
Overwrite
OSC Trigger Cntrl PB:
Overwrite
OSC Trigger Comm:
Overwrite
Table 5.15 Contact Input CFG
Contact Input Config
Contact Input Config Settings
Default Setting
Cin1:
52a
Cin2:
52b
Cin3:
BFI
Cin4:
Bkr Trouble
Cin5:
Remote Open
Cin6:
Remote Close
Cin7:
Remote Reset
Cin8:
user defined