Effective Date: 12/05
For more information visit:
www.eatonelectrical.com
Page 5-15
FP-5000
IL17569C
Page 5-15
Effective Date: 12/05
Display Setting
Description
Setpoint Range/ Value
Selection
Default
Setting
Selected
Value
Refer to
Sec. #
27A-2 UV Alarm
Auxiliary VT Undervoltage Alarm
Setting
Threshold V:
Select magnitude of undervoltage
required
10 to 250 Volts, disable
(1 Volt increments)
Disable
Delay (c):
Select delay time in cycles
0 to 9999 cycles
(1 cycle increments)
0
32-3 Power
Definition
Power Protection Settings 3
Direction:
Select the direction of the power
Forward, reverse, both
Reverse
Criterion:
Select if the threshold is based on
over or under power
Over, Under
Over
32-3 Power
Alarm
Power Alarm Settings
Threshold:
Select the magnitude of the power
required
2 to 4.0
pu
* or disable
(Increments of 1)
(401=off)
Disable
Delay (c):
Select the delay time in cycles
0 to 65535 cycles
(1 cycle increments)
10
81U-2 UF Alarm
Underfrequency Alarm Settings
Threshold:
Select threshold based on power
system frequency
45 to 65 Hz, disable
(0.01 increments)
Disable
Delay (c):
Select delay time in cycles
0 to 9999 cycles
(1 cycle increments)
0
81O-2 OF Alarm
Overfrequency Alarm Settings
Threshold:
Select threshold based on power
system frequency
45 to 65 Hz, disable
(0.01 increments)
Disable
Delay (c):
Select delay time in cycles
0 to 9999 cycles
(1 cycle increments)
0
* 1pu = 3 x CT secondary rating x VT secondary rating for wye; the square root of 3 x VT secondary rating x CT secondary
rating for delta
5.5.2.12
5.5.2.7
8.8
5.5.2.12
5.5.2.7
8.8
Alarms:
cont.
5.5.2.12
5.5.2.5
8.6.2
5.5.2.12
5.5.2.6
5.5.2.12
5.5.2.6