IL17569C
Page 5-18
FP-5000
Effective Date: 12/05
Page 5-18
For more information visit:
www.eatonelectrical.com
Effective Date: 12/05
Display Setting
Description
Setpoint Range/
Value Selection
Default
Setting
Selected
Value
Refer to
Sec. #
Current Demand
Current Demand Logging Setting
Interval (m):
Select interval for taking current
demand measurement in minutes
1 to 60 minutes
(Increments of 1)
15
Power Demand
Power Demand Logging Setting
Window:
Select type of power demand
window
Fixed or Slide
Fixed
Interval (m):
Select interval for taking power
demand measurement in minutes
1 to 60 minutes
(Increments of 1)
15
Event Log Enable
Even Log Settings for Pickups,
Contact Inputs and
I Pickup:
Select I Pickup to be logged
No, Yes
Yes
V Pickup:
Select V Pickup to be logged
No, Yes
No
Freq Pickup
Select Freq Pickup to be logged
No, Yes
No
PF Pickup:
Select PF Pickup to be logged
No, Yes
No
Unbal Pickup:
Select Unbal Pickup to be logged
No, Yes
No
SysAlm Pickup:
Select system alarm pickup to be
logged
No, Yes
No
Power Pickup:
Select power pickup to be logged
No, Yes
No
Logic Pickup:
Select logic pickup to be logged
No, Yes
No
Cin1:
Set Cin1 event to be logged
No, Yes
No
Cin2:
Set Cin2 event to be logged
No, Yes
No
Cin3:
Set Cin3 event to be logged
No, Yes
No
Cin4:
Set Cin4 event to be logged
No, Yes
No
Cin5:
Set Cin5 event to be logged
No, Yes
No
Cin6:
Set Cin6 event to be logged
No, Yes
No
Cin7:
Set Cin7 event to be logged
No, Yes
No
Cin8:
Set Cin8 event to be logged
No, Yes
No
Comm.:
Set Comm event to be logged
No, Yes
No
5.5.4
5.5.4
5.5.4
12.2.1
Logging Settings:
Phase time overcurrent (51P) and instantanious (50P-1 & 50P-2) device settings
Table 5.4 Logging Settings