FP-5000
Effective Date: 12/05
Table 2.1 Minimum List of Functions Which MUST be Programmed (continued)
Setting
Default
Setting
Incr
Display
User
Setting
51 IX TOC Shape:
XTRM
List
IT, I2T, I4T, FLAT, MOD, VERY, XTRM,
IECA, IECB, IECC
51 IX TOC Reset:
Calc
List
Inst, Calc, T Delay
51 IX TOC Direction:
Both
List
Forward, Reverse, Both
51 IX TOC Pickup:
0.50
0.01
0.1 to 4.0
pu
or Disable
51 IX TOC Time Mult:
1.00
0.01
0.05 to 10.0
50X-1 IX IOC 1 Pickup:
1.00
0.01
0.1 to 20.0
pu
or Disable
50X-1 IX IOC 1 Delay (c):
60
1
0 to 9999 cycles
50X-1 IX IOC 1 Direction:
Both
List
Forward, Reverse, Both
50X-1 IX IOC 2 Pickup:
2.00
0.01
0.1 to 20.0
pu
or Disable
50X-1 IX IOC 2 Delay (c):
6.00
1.00
0 to 9999 cycles
50X-1 IX IOC 2 Direction:
Both
List
Forward, Reverse, Both
51R IR TOC Shape:
XTRM
List
IT, I2T, I4T, FLAT, MOD, VERY, XTRM,
IECA, IECB, IECC
51R IR TOC Reset:
Calc
List
Inst, Calc, T Delay
51R IR TOC Direction:
Both
List
Forward, Reverse, Both
51R IR TOC Pickup:
0.50
0.01
0.1 to 4.0
pu
or Disable
51R IR TOC Time Mult:
1.00
0.01
0.05 to 10.0
50R-1 IR IOC 1 Pickup:
1.00
0.01
0.1 to 20.0
pu
or Disable
50R-1 IR IOC 1 Delay (c):
60
1
0 to 9999 cycles
50R-1 IR IOC 1 Direction:
Both
List
Forward, Reverse, Both
50R-1 IR IOC 2 Pickup:
2.00
0.01
0.1 to 20.0
pu
or Disable
50R-1 IR IOC 2 Delay (c):
600
1
0 to 9999 cycles
50R-1 IR IOC 2 Direction:
Both
List
Forward, Reverse, Both
46-2 I Unbal Alarm Threshold:
0.1
0.01
0.1 to 20.0
pu
, disable
46-2 I Unbal Alarm % (I2/I1):
40
1
2 to 40 percent
46-2 I Unbal Alarm Delay (c):
60
1
0 to 9999 cycles
47-2 V Unbal Alarm Threshold:
50
1
1 to 100 Volts, disable
47-2 V Unbal Alarm % (V2/V1):
40
1
2 to 40 percent
47-2 V Unbal Alarm Delay (c):
60
1
0 to 9999 cycles
IX Overcurrent
IR Residual Overcurrent
Unbal Alarm