Table 5.12 Protection
Phase Overcurrent
PH Settings
Default Setting
51P-1 PH TOC
Shape:
MOD
Reset:
Calc
Direction:
Both
Pickup:
1.00
Time Mult:
1.00
51P-2 PH TOC
Shape:
MOD
Reset:
Calc
Direction:
Both
Pickup:
1.00
Time Mult:
2.00
Vrestraint:
Disable
50P-1 PH IOC 1
Pickup:
2.00
Delay (c):
0
Direction:
Both
50P-1 PH IOC 2
Pickup:
3.00
Delay (c):
15
Direction:
Both
IX Overcurrent
IX Settings
Default Setting
51X IX TOC
Shape:
XTRM
Reset:
Calc
Direction:
Both
Pickup:
0.50
Time Mult:
1.00
50X-1 IX OC 1
Pickup:
1.00
Delay (c):
60
Direction:
Both
50X-1 IX OC 2
Pickup:
2.00
Delay (c):
6.00
Direction:
Both
IR Overcurrent
IR Settings
Default Setting
51R IR TOC
Shape:
XTRM
Reset:
Calc
Direction:
Both
Pickup:
0.5
Time Mult:
1.00
50R-1 IR IOC 1
Pickup:
1.00
Delay (c):
60
Direction:
Both
50R-1 IR IOC 2
Pickup:
2.00
Delay (c):
600
Direction:
Both
47-1 V Unbal
47-1 Voltage Unbalance Alarm Settings
Default Setting
Threshold:
Disable
% (I2/I1):
20
Delay (c):
600
46-1 Current Unbal
46-1 Current Unbalance Alarm Settings
Default Setting
Threshold:
Disable
% (V2/V1):
20
Delay (c):
600