“IX Measured OC” Display:
“IR Residual OC” Display:
IX Measured OC
51X IX TOC Curve
51X IX TOC Setting
50X-1 IX IOC 1
50X-2 IX IOC 2
51X IX TOC Curve
Shape: XTRM
Reset: Calc
Direction: Both
51X IX TOC Setting
Pickup (pu): .50
Time Mult: 1.00
50X-2 IX IOC 2
Pickup (pu): 2.00
Delay (c): 600
Direction: Both
50X-1 IX IOC 1
Pickup (pu): 2.00
Delay (c): .60
Direction: Both
IR Residual OC
51R IR TOC Curve
51R IR TOC Setting
50R-1 IR IOC 1
50R-2 IR IOC 2
51R IR TOC Curve
Shape: XTRM
Reset: Inst
Direction: Both
51R IR TOC Setting
Pickup (pu): 0.10
Time Mult: 1.00
50R-2 IR IOC 2
Pickup (pu): 2.00
Delay (c): 600
Direction: Both
50R-1 IR IOC 1
Pickup (pu): 2.00
Delay (c): 60
Direction: Both