IL17569C
Page 5-22
FP-5000
Effective Date: 12/05
Page 5-22
For more information visit:
www.eatonelectrical.com
Effective Date: 12/05
Display Setting
Description
Setpoint Range/
Value Selection
Default
Setting
Selected
Value
Refer to
Sec. #
Output Rly3
Output Relay 3 Settings
Function:
Select logic output function for
Output Rly3
OR, AND, NOR, NAND,
disable
OR
Dropout:
Select relay state after trip occurs
Latched, unlatched, off delay Latched
Off Delay (c):
Select delay for Relay to dropout
after trip event clears
1
0 to 600 cycles
(1 cycle increments)
0
IN1:
Select logic input IN1 for Output
Rly3
*See Logic Input Options
Table 5.10
Trip, BF
IN2:
Select logic input IN2 for Output
Rly3
*See Logic Input Options
Table 5.10
Unused
IN3:
Select logic input IN3 for Output
Rly3
*See Logic Input Options
Table 5.10
Unused
IN4:
Select logic input IN4 for Output
Rly3
*See Logic Input Options
Table 5.10
Unused
Output Rly4
Output Relay 4 Settings
Function:
Select logic output function for
Output Rly4
OR, AND, NOR, NAND,
disable
Disable
Dropout:
Select relay state after trip occurs
Latched, unlatched, off delay Unlatched
Off Delay (c):
Select delay for Relay to dropout
after trip event clears
1
0 to 600 cycles
(1 cycle increments)
0
IN1:
Select logic input IN1 for Output
Rly4
*See Logic Input Options
Table 5.10
Unused
IN2:
Select logic input IN2 for Output
Rly4
*See Logic Input Options
Table 5.10
Unused
IN3:
Select logic input IN3 for Output
Rly4
*See Logic Input Options
Table 5.10
Unused
IN4:
Select logic input IN4 for Output
Rly4
*See Logic Input Options
Table 5.10
Unused
Output Configuration Settings:
cont.
5.5.6
9.2
9.6
5.5.6
9.2
9.6
1
This setting is only used if the “Dropout” setting is set to “Off Delay.”