SCWD-QS (12/16)
Page 9
Figure 3. Compressor Unit Clearance
Placement instructions for other pieces of equipment that make up the EarthLinked
®
System are
included with those pieces of equipment and are listed in this manual under
Equipment Manuals.
3) Refrigeration
After the EarthLinked
®
compressor unit and other system components are placed, the refrigeration
system tubing is run from the compressor unit to the other components, as appropriate. Figure 4
illustrates the refrigeration and electrical connection points for the compressor unit.
IMPORTANT!
EarthLinked
®
compressor units that provide space cooling shall be
equipped with an EarthLinked
®
Hybrid Cooling Module (HCM) when:
(1) Required by the performance tables; OR
(2) System is in a Cooling dominant application where soil thermal
conductivity is unknown or known to be poor (less than 1
BTU/hr.ft.°F). Examples of such soils are light dry soil, dry sand, peat
and organic soils, dry clay and hardpan; OR
(3) In any system where soil thermal conductivity is unknown or known
to be poor (see (2) for definition) and ambient outdoor temperatures
have exceeded the outdoor summer design temperature conditions
for a continuous system run time of at least 7 hours.
IMPORTANT!
EarthLinked
®
compressor units that provide space heating shall be
equipped with a Heating Performance Enhancement kit (HPE) when
required by the performance tables.
Summary of Contents for SCWD-024-1C
Page 15: ...SCWD QS 12 16 Page 15 Figure 7 SCWD Compressor Unit Electrical Schematic Diagram 230 1 60...
Page 16: ...SCWD QS 12 16 Page 16 Figure 8 SCWD Compressor Unit Electrical Schematic Diagram 230 3 60...
Page 17: ...SCWD QS 12 16 Page 17 Figure 9 SCWD Hydronic Heating Cooling Water Heating Sytem Application...
Page 20: ...SCWD QS 12 16 Page 20 Figure 11 SureStart Mode of Operation...
Page 31: ...SCWD QS 12 16 Page 31 Figure 14 Disassembled Plug Connector...
Page 38: ...SCWD QS 12 16 Page 38 Figure 23 SCWD Internal Flow Schematic...
Page 39: ...SCWD QS 12 16 Page 39 Figure 24 SCWD Piping...
Page 41: ...SCWD QS 12 16 Page 41 Figure 25 Evacuation of SCWD System...
Page 43: ...SCWD QS 12 16 Page 43 Figure 26 Initial Charge of SCWD System...
Page 45: ...SCWD QS 12 16 Page 45 Figure 27 Final Charge of SCWD System...
Page 48: ...SCWD QS 12 16 Page 48 Figure 31 Start Up Process...