SCWD-QS (12/16)
Page 58
Triple Evacuation
Triple evacuation is implemented to evacuate a system to a deep vacuum. It is accomplished by
evacuating a system to a vacuum of 1500 microns, and then bleeding a small amount of dry nitrogen
into the system. The nitrogen is then blown out to the atmosphere. The system is then evacuated
until the vacuum is again reduced to 1500 microns. This procedure is repeated three times, with the
last vacuum level reaching a deep vacuum of 400 microns, which is held for 10 to 15 minutes. The
following is a detailed description of the triple evacuation.
1. Attach an electronic micron gauge to the system. The best place is as far from the vacuum
port as possible, which would be the access port on a service valve on the EarthLinked
®
compressor unit.
2. Let the vacuum pump run until the digital vacuum gauge reaches
1500 microns.
After
reaching 1500 microns, isolate the digital vacuum gauge.
3. Purge hoses with nitrogen. Then, allow a small amount of dry nitrogen to enter the system
until the LP gauge shows about 5 psig. This small amount of dry nitrogen will fill the system
and mix with the other vapors.
4. Release system pressure to 0 psig and close the valve. Then open the isolation valve on the
digital vacuum gauge.
5. Open the vacuum pump valve and start the vapor removal process from the system again.
Let the vacuum pump run until the vacuum is again reduced to
1500 microns.
Repeat Step 3.
6. After nitrogen has been added to the system a
second time
, open the vacuum pump valve
and again remove the vapor. Operate the vacuum pump until the vacuum on the electronic
micron gauge reads
400 microns.
7. Once the micron gauge reads
400 microns for 10 to 15 minutes
, isolate the micron gauge.
The system must not exceed 500 microns in 15 minutes. If it does,
repeat step 6
.
8. Then charge the system in accordance with the initial refrigerant charging procedure.
Summary of Contents for SCWD-024-1C
Page 15: ...SCWD QS 12 16 Page 15 Figure 7 SCWD Compressor Unit Electrical Schematic Diagram 230 1 60...
Page 16: ...SCWD QS 12 16 Page 16 Figure 8 SCWD Compressor Unit Electrical Schematic Diagram 230 3 60...
Page 17: ...SCWD QS 12 16 Page 17 Figure 9 SCWD Hydronic Heating Cooling Water Heating Sytem Application...
Page 20: ...SCWD QS 12 16 Page 20 Figure 11 SureStart Mode of Operation...
Page 31: ...SCWD QS 12 16 Page 31 Figure 14 Disassembled Plug Connector...
Page 38: ...SCWD QS 12 16 Page 38 Figure 23 SCWD Internal Flow Schematic...
Page 39: ...SCWD QS 12 16 Page 39 Figure 24 SCWD Piping...
Page 41: ...SCWD QS 12 16 Page 41 Figure 25 Evacuation of SCWD System...
Page 43: ...SCWD QS 12 16 Page 43 Figure 26 Initial Charge of SCWD System...
Page 45: ...SCWD QS 12 16 Page 45 Figure 27 Final Charge of SCWD System...
Page 48: ...SCWD QS 12 16 Page 48 Figure 31 Start Up Process...