8. Grounded Windings
Test the compressor motor for a grounded winding. The check should be made using an
ohmmeter capable of measuring very high resistance on a VOM. The resistance
between windings and the housing is one million to three million ohms for an
ungrounded
winding.
Attach one lead to the compressor case on a bare metal tube or ground terminal, and to
each compressor terminal as shown in Figure 34. A short circuit at a high voltage
terminal indicates a motor defect (grounded).
Figure 34. Compressor Motor Grounded Winding Test
9.
Compressor not pumping.
Connect gauge block hoses to the suction and discharge pressure ports in the
compressor unit. Read pressure gauges to affirm that system is pressurized with
refrigerant. Turn on power to compressor unit and run unit. Observe pressure gauges. If
pressures on both gauges remain the same, compressor is not pumping and there is a
possible internal failure. See System Troubleshooting Chart.
Summary of Contents for SCWD-024-1C
Page 15: ...SCWD QS 12 16 Page 15 Figure 7 SCWD Compressor Unit Electrical Schematic Diagram 230 1 60...
Page 16: ...SCWD QS 12 16 Page 16 Figure 8 SCWD Compressor Unit Electrical Schematic Diagram 230 3 60...
Page 17: ...SCWD QS 12 16 Page 17 Figure 9 SCWD Hydronic Heating Cooling Water Heating Sytem Application...
Page 20: ...SCWD QS 12 16 Page 20 Figure 11 SureStart Mode of Operation...
Page 31: ...SCWD QS 12 16 Page 31 Figure 14 Disassembled Plug Connector...
Page 38: ...SCWD QS 12 16 Page 38 Figure 23 SCWD Internal Flow Schematic...
Page 39: ...SCWD QS 12 16 Page 39 Figure 24 SCWD Piping...
Page 41: ...SCWD QS 12 16 Page 41 Figure 25 Evacuation of SCWD System...
Page 43: ...SCWD QS 12 16 Page 43 Figure 26 Initial Charge of SCWD System...
Page 45: ...SCWD QS 12 16 Page 45 Figure 27 Final Charge of SCWD System...
Page 48: ...SCWD QS 12 16 Page 48 Figure 31 Start Up Process...