SCWD-QS (12/16)
Page 29
The SCWD compressor unit Internal Heat Recovery System contains a water high temperature
control. It is factory set to 140°F. The Heat Recovery System also contains a refrigerant low
temperature which is factory set at 130°F. Also, a freeze protection control is designed to operate the
circulating pump when water temperature drops to 40°F, in order to provide water circulation
independent of compressor operation.
The GSTE storage water heaters are available in 60, 80 and 119 US gallon capacities, all of which
have a 4.5 kW electric heating element, which provides the following recovery rates for increases in
water temperature.
ΔT
30
40
50
60
70
80
90
GPH
62
46
37
31
26
23
21
*
ΔT in ºF; GPH in U.S. Gallons per hour.
WARNING!
The compressor unit and associated water piping must be in an
environment maintained at a temperature of at least 40°F to avoid the
potential freeze-up problems which can cause equipment failure and
damage to the occupied structure.
Summary of Contents for SCWD-024-1C
Page 15: ...SCWD QS 12 16 Page 15 Figure 7 SCWD Compressor Unit Electrical Schematic Diagram 230 1 60...
Page 16: ...SCWD QS 12 16 Page 16 Figure 8 SCWD Compressor Unit Electrical Schematic Diagram 230 3 60...
Page 17: ...SCWD QS 12 16 Page 17 Figure 9 SCWD Hydronic Heating Cooling Water Heating Sytem Application...
Page 20: ...SCWD QS 12 16 Page 20 Figure 11 SureStart Mode of Operation...
Page 31: ...SCWD QS 12 16 Page 31 Figure 14 Disassembled Plug Connector...
Page 38: ...SCWD QS 12 16 Page 38 Figure 23 SCWD Internal Flow Schematic...
Page 39: ...SCWD QS 12 16 Page 39 Figure 24 SCWD Piping...
Page 41: ...SCWD QS 12 16 Page 41 Figure 25 Evacuation of SCWD System...
Page 43: ...SCWD QS 12 16 Page 43 Figure 26 Initial Charge of SCWD System...
Page 45: ...SCWD QS 12 16 Page 45 Figure 27 Final Charge of SCWD System...
Page 48: ...SCWD QS 12 16 Page 48 Figure 31 Start Up Process...