SCWD-QS (12/16)
Page 51
Note:
Cautiously and carefully feel the top of the compressor to see if it has overheated.
If it is hot, the internal overload may be open. You may have to wait several hours for it
to reset before proceeding.
If the compressor draws a high amperage and does not start (amperage is approximately
locked rotor amperage
– LRA (See Figure 7)), the compressor is locked mechanically
and should be removed from the system and replaced. Verify before removing!
7. Motor Circuit Testing
Using a digital volt-ohmmeter (VOM), measure the resistance across the compressor
windings terminals as shown in Figure 33. The power leads to the compressor must be
disconnected before taking an electrical measurement. A good rule of thumb for single
phase compressors is that start winding resistance (R
2
) is 3 to 5 times greater than run
winding resistance (R
1
).
Figure 33. Compressor Motor Circuit Testing
Summary of Contents for SCWD-024-1C
Page 15: ...SCWD QS 12 16 Page 15 Figure 7 SCWD Compressor Unit Electrical Schematic Diagram 230 1 60...
Page 16: ...SCWD QS 12 16 Page 16 Figure 8 SCWD Compressor Unit Electrical Schematic Diagram 230 3 60...
Page 17: ...SCWD QS 12 16 Page 17 Figure 9 SCWD Hydronic Heating Cooling Water Heating Sytem Application...
Page 20: ...SCWD QS 12 16 Page 20 Figure 11 SureStart Mode of Operation...
Page 31: ...SCWD QS 12 16 Page 31 Figure 14 Disassembled Plug Connector...
Page 38: ...SCWD QS 12 16 Page 38 Figure 23 SCWD Internal Flow Schematic...
Page 39: ...SCWD QS 12 16 Page 39 Figure 24 SCWD Piping...
Page 41: ...SCWD QS 12 16 Page 41 Figure 25 Evacuation of SCWD System...
Page 43: ...SCWD QS 12 16 Page 43 Figure 26 Initial Charge of SCWD System...
Page 45: ...SCWD QS 12 16 Page 45 Figure 27 Final Charge of SCWD System...
Page 48: ...SCWD QS 12 16 Page 48 Figure 31 Start Up Process...