SCWD-QS (12/16)
Page 8
Figure 2. General Layout of System Components
2) Compressor Unit Placement
EarthLinked
®
SCWD compressor units may be located inside only. When placing it inside,
place it on a level, hard surface.
Avoid placing the compressor unit in or near sound sensitive areas of the residence.
Attic installations must include an auxiliary condensate pan with drain, and suspension
from rafters with suspension isolators.
Clearance around the unit for service is illustrated in Figure 3. However, local codes and
applicable regulations take precedence.
Compressor unit or other refrigerant-containing system components located indoors shall
be in a location which (1) is an
unoccupied space
, or (2) is served by the circulating air
system, or (3) provides 280 cu. ft. of open space per nominal ton of rated system capacity.
The
2012 International Mechanical Code
defines residential occupancy as including
permanent provisions for living, sleeping, eating cooking, and sanitation. Consult local
code authorities to define
unoccupied space
for the specific installation.
Summary of Contents for SCWD-024-1C
Page 15: ...SCWD QS 12 16 Page 15 Figure 7 SCWD Compressor Unit Electrical Schematic Diagram 230 1 60...
Page 16: ...SCWD QS 12 16 Page 16 Figure 8 SCWD Compressor Unit Electrical Schematic Diagram 230 3 60...
Page 17: ...SCWD QS 12 16 Page 17 Figure 9 SCWD Hydronic Heating Cooling Water Heating Sytem Application...
Page 20: ...SCWD QS 12 16 Page 20 Figure 11 SureStart Mode of Operation...
Page 31: ...SCWD QS 12 16 Page 31 Figure 14 Disassembled Plug Connector...
Page 38: ...SCWD QS 12 16 Page 38 Figure 23 SCWD Internal Flow Schematic...
Page 39: ...SCWD QS 12 16 Page 39 Figure 24 SCWD Piping...
Page 41: ...SCWD QS 12 16 Page 41 Figure 25 Evacuation of SCWD System...
Page 43: ...SCWD QS 12 16 Page 43 Figure 26 Initial Charge of SCWD System...
Page 45: ...SCWD QS 12 16 Page 45 Figure 27 Final Charge of SCWD System...
Page 48: ...SCWD QS 12 16 Page 48 Figure 31 Start Up Process...