SCWD-QS (12/16)
Page 26
The manufacturer’s specific instructions and industry standards always take precedence when
introducing propylene-glycol to the system.
Calculate the quantity of inhibited propylene-glycol (fluid) required to achieve the desired results.
Introduce a sufficient quantity of water to the system and pressure check to ensure a sealed
system.
Drain some water from the system to provide enough volume for the calculated amount of
fluid.
Add the correct amount of fluid and any water needed to completely refill the system, allowing
for liquid expansion due to operating temperature.
Circulate the inhibited propylene-glycol antifreeze solution for at least 24 hours to ensure
complete mixing. Check the liquid concentration to assure that the correct mixture is obtained.
Note:
ETI has a temperature switch available by order, to achieve lower hydronic temperatures.
IMPORTANT!
Always follow the propylene-
glycol manufacturer’s instructions
concerning the water quality specifications before filling the water
circulating system.
IMPORTANT!
Freeze protection is provided on all SCWD compressor units by means
of a factory installed thermal switch that turns the system OFF when
heat exchanger outlet water drops to 38°F.
Summary of Contents for SCWD-024-1C
Page 15: ...SCWD QS 12 16 Page 15 Figure 7 SCWD Compressor Unit Electrical Schematic Diagram 230 1 60...
Page 16: ...SCWD QS 12 16 Page 16 Figure 8 SCWD Compressor Unit Electrical Schematic Diagram 230 3 60...
Page 17: ...SCWD QS 12 16 Page 17 Figure 9 SCWD Hydronic Heating Cooling Water Heating Sytem Application...
Page 20: ...SCWD QS 12 16 Page 20 Figure 11 SureStart Mode of Operation...
Page 31: ...SCWD QS 12 16 Page 31 Figure 14 Disassembled Plug Connector...
Page 38: ...SCWD QS 12 16 Page 38 Figure 23 SCWD Internal Flow Schematic...
Page 39: ...SCWD QS 12 16 Page 39 Figure 24 SCWD Piping...
Page 41: ...SCWD QS 12 16 Page 41 Figure 25 Evacuation of SCWD System...
Page 43: ...SCWD QS 12 16 Page 43 Figure 26 Initial Charge of SCWD System...
Page 45: ...SCWD QS 12 16 Page 45 Figure 27 Final Charge of SCWD System...
Page 48: ...SCWD QS 12 16 Page 48 Figure 31 Start Up Process...