A p p e n d i x E : W L S 9 0 4 P L W i r e l e s s M o t i o n D e t e c t o r I n s t a l l a t i o n I n s t r u c t i o n s
5 7
then shut down for three minutes. If motion is detected
again during the shutdown time, the unit will not trans-
mit the event to the receiver. The detector will thus
remain in the shutdown mode until three minutes after
the first motion detected was transmitted. The detector
will transmit detected motion every three minutes.
The High Traffic Shutdown Mode affects testing the
motion detector in two ways:
When performing the
module placement test
, the
unit must be tampered by removing the unit from the
backplate and replacing it. The placement test cannot
be performed by creating motion in front of the device.
When performing a
system test
, the unit must be
left idle for three minutes before testing can be per-
formed. Once three minutes has passed, create motion
in front of the detector to see if the device is both
detecting motion and transmitting to the receiver.
NOTE:
Refer to the PC5132 and PC5010 Installa-
tion Instructions for UL/ULC requirements. For UL/
ULC installations where the WLS904PL is used on
entry or exit delay zones, the entry delay must
not be longer than 45 seconds, and the exit delay
must not be longer than 60 seconds.
Motion Detector Transmission Delay
A motion detector transmission is always delayed by six
seconds. This is necessary to prevent false alarms caused
by a motion sensor transmitting before a delay zone has
a chance to report. This six-second delay cannot be
altered or disabled.
Walk Test Mode
The motion detector has a walk test mode which will
activate an LED for testing purposes. During normal
operation, the LED will not turn on.
To put the detector in walk test mode, create a tamper
by removing the detector from its backplate and then
replacing it. Each time the detector senses motion, it will
turn on the red LED. Five seconds after motion is
detected, the detector will send a signal to the receiver,
and the LED will flash rapidly 5 times. The detector will
be in walk test mode until it has sent 10 transmissions.
To verify the pet immunity of the detector place the ani-
mal(s) within the coverage area and then move out of the
zone. Encourage the pet to move around as it normally
would and ensure that it moves across the detection pat-
tern of the detector. Verify that no alarm is initiated.
To test for catch performance of humans, create motion
in the entire area where coverage is desired by walking
perpendicular to the lens pattern. Should the coverage
be incomplete, readjust or relocate the detector.
NOTE:
The Walk Test Mode will override the
High Traffic Shutdown Mode.
Battery Installation
• This system is designed to work with the Energizer
Lithium EL123AP, Tekcell CR123A Lithium or Pana-
sonic Lithium CR123A battery. Do not install any
other type. The reliability of the security system
depends on its batteries, and “no name” or
generic brand batteries may not provide the best
quality and dependability.
• Use fresh batteries. Buy batteries that have a “best
before” date of two years or more from your pur-
chase date.
• When disposing of used batteries, follow the
instructions and precautions printed on the batter-
ies. Many cities and communities have collection
sites or services for used household batteries. Con-
tact your municipal offices for information on the
disposal of used batteries.
Remove the motion detector from its mounting plate
by holding the sensor by its sides and pushing up.
Remove the battery cover. Install new battery. Place
the battery cover back on. Secure the battery cover
with the small screw provided. Replace the sensor on
its mounting plate, making sure it snaps into place.
After the battery is installed, the detector will take 60
seconds to warm up. During this time the LED will
flash slowly.
NOTE:
Please refer to the WLS904PL-433 Installation Instructions for more details.
TOP VIEW
SIDE VIEW
Detection Pattern
"Fast" Setting - 40ft x 40ft
"Slow" Setting - 35ft x 35ft