A p p e n d i x C : U L L i s t e d G r a d e A C o n t r o l U n i t R e q u i r e m e n t s
5 4
Table2: Contact ID Zone Alarm/Resto-
ral Event Codes (as per ADEMCO):
Program any of these codes for zone alarms/restorals
when using the standard (non-automatic) Contact ID
reporting format.
Table 3: SIA Format Automatic
Zone Alarm/Restoral Codes
A p p e n d i x C : U L L i s t e d G r a d e A
C o n t r o l U n i t R e q u i r e m e n t s
• Installer should verify communication format
between control unit and receiver.
• Entry delay must not exceed 45 seconds.
• Exit delay must not exceed 60 seconds.
• Minimum bell cutoff time is 4 minutes.
• Keyswitch (if used) must be mounted in a pro-
tected area.
• ‘Quick Exit’ feature must be disabled.
• ‘Bell Squawk on Trouble’ feature must be enabled.
• Minimum ‘Dialing Attempt’ must be 5 and maxi-
mum 10.
• Hardwired zones must be EOL configuration.
• ‘Code Required to Bypass Zones’ must be enabled.
• ‘Bypass Status not Displayed While Armed’ option
selected.
• ‘Test Transmission Cycle’ must be set for daily
transmission.
• ‘Keypad Lockout’ must be programmed.
• ‘Temporal Three Fire Signal’ must be enabled.
• ‘Closing Confirmation’ must be enabled.
• ‘UL Communications Priority’ must be enabled.
• ‘One time 1-hour User Enabled DLS Window’ must
be enabled.
• ‘Answering Machine/Double Call’ option must
NOT be enabled.
• ‘Wireless Supervisory Window’ must be pro-
grammed 4 hours or less.
• ‘RF Jamming Detection Zone’ must be pro-
grammed; zone type ‘Instant’.
NOTE:
This control unit is to be checked by a qualified technician at least once every 3 years.
Medical Alarms
(1)34
Entry
/
Exit
(1)AA Medical
(1)35 Day / Night
(1)A1 Pendant Transmitter
(1)36 Outdoor
(1)A2 Fail to Report In
(1)37 Tamper
Fire Alarms
(1)38 Near Alarm
(1)1A Fire Alarm
General Alarms
(1)11 Smoke
(1)4A General Alarm
(1)12 Combustion
(1)43 Exp. module failure
(1)13 Water Flow
(1)44 Sensor tamper
(1)14 Heat
(1)45 Module Tamper
(1)15 Pull Station
(1)4A Cross Zone Police Code
(1)16 Duct
24 Hour Non-Burglary
(1)17 Flame
(1)5A 24 Hour non-Burg
(1)18 Near Alarm
(1)51 Gas detected
Panic Alarms
(1)52 Refrigeration
(1)2A Panic
(1)53 Loss of Heat
(1)21 Duress
(1)54 Water Leakage
(1)22 Silent
(1)55 Foil Break
(1)23 Audible
(1)56 Day Trouble
Burglar Alarms
(1)57 Low bottled Gas level
(1)3A Burglary
(1)58 High Temp
(1)31 Perimeter
(1)59 Low Temp
(1)32 Interior
(1)61 Loss of Air Flow
(1)33 24 Hour
Zone Definition
SIA Auto Rep
Codes*
Zone Alm/Rest.
Delay, Instant, Interior, Delay
Stay/Away, Interior Stay/Away,
24-hr Burg.
BA-ZZ/BH-ZZ
24-hr Fire
FA-ZZ/FH-ZZ
24-hr Supervisory Buzzer
UA-ZZ/UH-ZZ
24-hr Sprinkler
SA-ZZ/SH-ZZ
24-hr Gas
GA-ZZ/GH-ZZ
24-hr Heat
KA-ZZ/KH-ZZ
24-hr Medical
MA-ZZ/MH-ZZ
24-hr Emergency (non-medical)
QA-ZZ/QH-ZZ
24-hr Waterflow
WA-ZZ/WH-ZZ
24-hr Freeze
ZA-ZZ/ZH-ZZ
24-hr Holdup
HA-ZZ/HH-ZZ
24-hr Panic
PA-ZZ/PH-ZZ
Latching 24-hr
BA-ZZ/BH-ZZ
* ZZ = zones 01-32