3 6
Swinger Shutdown Enable . . . . . . . . . . . . . . . . . Section [101] to [132], Option [6]
Transmission Delay Enable . . . . . . . . . . . . . . . . . Section [101] to [132], Option [7]
Wireless Zone . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [101] to [132], Option [8]
2.3.3 Enrolling
Hardwired
Zones
You can install up to two hardwired zones on the NT9010 system. To make the wiring con-
nections for these zones, please see
Connecting Zone Wiring – Hardwired
on page 7.
You must also enroll the hardwired zones on the system.
To do this, in Flash Programming enter serial number [200001] for the first hardwired zone,
and [200002] for the second hardwired zone. The NT9010 system will automatically assign
the hardwired zone to the next available zone number.
If you need to change the zone assignment of the hardwired zones, you can do this in the
Advanced programming sections:
1. Enter programming section [807].
2. Enter sub-section [091] for the first hardwired zone, or sub-section [092] for the sec-
ond hardwired zone.
3. Enter the 2-digit number of the zone that will be hardwired.
NOTE:
Serial numbers for hardwired zones are only required for flash program-
ming. DO NOT enter a serial number for a hardwired zone through Advanced
Programming.
NOTE:
Entering a zone as a hardwired zone will override any wireless device
serial number that may be programmed for the zone.
NOTE:
Fire zones are not supported as hardwired zones.
2.3.4 Wireless
Device Serial
Numbers
Normally, you will use the NT9010 Flash Programming to enter device serial numbers. If you
need to delete a device from a zone, or replace a device, you can use the advanced pro-
gramming section. To add, replace, or delete devices:
1. From Installer’s Programming, enter section [804]
2. Enter the 2-digit number of the zone you want to delete (01 - 32). The system
announces the current serial number for the zone.
3. Enter the new serial number for the zone. To delete a device, enter [000000]. The
wireless device for the zone will be removed.
NOTE:
You may need to remove power from the system and then restore it to
clear troubles caused by deleted zones.
2.3.5 Wireless Zone
Supervision
NOTE:
The RF Jam Detect zone, hardwired zones, and Panic Pendants must
have the supervision option disabled.
Wireless Supervisory Window
Each wireless zone will send a supervisory signal every 64 minutes. If the receiver does not
receive a signal within the time programmed for the
Wireless Supervisory Window
, it
will generate a supervisory fault.
To program the wireless supervisory window, from Advanced Programming:
1. Enter section [804].
2. Enter sub-section [81].
3. Enter the time period for the supervisory window (valid entries are 01-24 hours).
4. To exit press [#].