Product information
Products: safety technology
SafeLine
redaction 11 date 10.04.09 page 39 from 48
General t
echnical data
Electrical characteristics
Operation voltage U
B
24V DC on A1/ A2 central module for complete unit
Margins U
B
85 - 110%
Ripple U
B
Max. 10 %
Power consumption at U
B
Number of Module dependent
Environment conditions
Operation temperature
-10 to +60°C
according DIN IEC 60068-2-3
Storage temperature
-40 to +85°C
according DIN IEC 60068-2-3
Vibration resistance 3 axis
Sinus 10–55Hz, 0,35mm, 10 cycles, 1 octave /min
Cable cross section max.
1 x 1,0mm
2
, Spring load clamp, pluggable
Housing material
Galvanized sheet steel, powder coated
Protection class
installation in a closed cabinet only with min
.
≥
IP54
Inputs
Maximum voltage at the inputs
24V DC –15%, + 10%
Inputs current consumption
Maximum 3,5mA
Residual voltage at load using semiconductor output and failure A2 disconnected.
Residual voltage at 5mA load current (4,8Kohm)
< 4,5V
Residual voltage at 10mA load current (2,4Kohm)
< 2,5V
Residual voltage at 20mA load current (1,2Kohm)
< 1,0V
Residual voltage, residual current and minimum current using semiconductor output.
Residual current at output short circuit to A2 (0V)
< 5µA
Residual voltage at 1A load
< 200mV
Residual voltage at 0,5A load
< 100mV
Residual voltage at minimum load (
≤
0,1A)
< 50mV
Minimum current
1mA
Necessary electromagnetic interference suppression of
the external output load for all semiconductor outputs
Recovery diode (fly back diode)
DNSL-ZM
t
echnical data
Internal fuse
6A, automatic reset
Power consumption at A1, A2
Max 2,9W
Switch and continuous current output O1, resistive load
Max. 100mA
Maximum Frequency for FrqIn
(O1 as input)
1200Hz
Technical data of outputs O2 – O5
Switching and continuous current inductive and resistive load Max. 1A, short and over load protected
Total switching and continuous current for all outputs
Max. 2A
Minimum switching current
10mA
Mechanical product life
2 x 10
6
switching cycle
Electrical product life with resistive load, 1A
8 x 10
5
switching cycle, switch-off without current.
Electrical product life with inductive load, 1A, cos
ϕ
= 0,4
5 x 10
5
switching cycle switch-off without current.
Reaction time, drop-out time
≤
≤
≤
≤
10mS
Maximum switching rate
1800 cycles / h
Technical data of outputs O6 and O7
Switching and continuous current inductive and resistive load Max. 0,25A, short and over load protected
Total switching and continuous current
Max. 0,4A
Summary of Contents for SafeLine DNSL-ZM
Page 1: ...SafeLine Product information Safety for men and machines...
Page 48: ......