Product information
Products: safety technology
SafeLine
redaction 11 date 10.04.09 page 34 from 48
DNSL-RM, DNSL-RM 230: Relay modules
DNSL-RM
DNSL-RM: Connection scheme
DNSL-RM-230
82
K1
K2
K3
K4
K1
K2
K3
K4
Power
Info
11 12 13 14 23 24 33 34 43 44
53 54 63 64 73 74 83 84 81
Ausgangskontakte / Ouput contacts
DNSL-RM-230: Connection scheme
K1
K2
K3
K4
K1
K2
K3
K4
Power
Info
13 14 23 24 33 34 43 44
53 54 63 64 73 74 83 84
Ausgangskontakte / Ouput contacts
Outputs usage
Paired Relays
DNSL-RM
Paired Relays
DNSL-RM-230
The DNSL-RM module contains 4 Relays.
Relays 11, and 22 have 2 NO and 1 NC con-
tact each.
Relays 12, and 21 have 2 NO contact each.
DNSL-RM-230 has not the NC contacts
11/12 and 81/82
The relays may be configured as follows:
Paired Relays
safety category 4,
REL11, REL12 controlled by S1
REL21, REL22 controlled by S2
The virtual clamps
S1, S2
are displayed in the
wiring layer only if the function paired output is
selected in the parameter mask.
Single Relays
DNSL-RM
Single Relays
DNSL-RM-230
Single Relays
safety category 2.
REL11, 12, 21 and 22
individually activated by
REL11, REL12, REL21 and REL22.
A mixed usage is possible.
Note:
All output contacts will be monitored
constantly for wrong behavior on switch off,
independent of the function. If an error is de-
tected on one of the contacts, all outputs of
Safeline will be switched off.
Parameter mask
Rel2_1, 2_2
:
Fields for the labeling of the outputs block
Rel11
: R11, R12, R13, R14, R23, R24
Rel12
:
R33, R34, R43, R44
Rel21
:
R53, R54, R63, R64
Rel22
: R81, R82 R73, R74, R83, R84
Fields for the labeling the contact terminals
Rel1, Rel2
1 chan., safe:
paired redundant outputs
2 chan., unsafe:
single relay outputs
OK
: Mask safe and loose
Abbrechen
: Mask loose without safe