redaction 11 date 10.04.09 page 12 from 48
Parameter mask
DNCO Parameter mask
: Mask save and close.
Selecting DNCO mask is available in every central module mask.
Description of the parameter mask: See page 8 and 9.
DNCO function: Parameter mask
Two frequency tables containing up to 48 values each.
These values define the maximum monitored speeds. This frequency values
are the frequencies of the encoder of the drive measurement system by the
corresponding speed.
Monitoring 8, 16 or 48 speed’s is possible and can be selected via the central
module mask “DNCO Terminals”. The necessary inputs to select one from 8,
16 or 48 speeds can be used at the central module or at the motion monitoring
module DNSL-DS. For 8 value there are 3 input necessary, for 16 value 4
inputs and for 48 value 6 inputs.
A frequency value has to be entered in every field of the selected table.
With the selection 16 the frequency value 01 to 15 can be automatically calcu-
lated, if the maximal value in field DNCO1_16 is entered.
After this the button
for the left table and
for the right
have to be activated.
A %-value (0 to 20%) can be sum up to all value in the table, if in the field
“Tolerance” a value was entered and the button
will be activated.
For every frequency table the encoder input at motion monitoring equipment
has to be defined. The selection has to be done vie Encoder1/2.
DS to Teach
: For this function see DNSL-ZMA.
Example:
DNCO1 table via DNSL-DS
D1
B11
D2
D3
D4
D5
D6
B12
B13
B14
B21
B22
DNSL-DS
DNCO1
SH-K
TK
Steuergerät
Control
device
DNCO2 table via central module
D1
I1
D2
D3
D4
D5
D6
I2
I3
I4
I5
I6
DNSL-ZM
ZMB
ZMT
ZMA
ZMK
ZMR
DNCO1
SH-K
TK
Steuergerät
Control
device
Position monitoring of axis with DNSL-DS
Usage DNCO mask for the configuration
The right side of the mask is used for the position moni-
toring.
The motion control DNSL-DS, DR is able to monitor the
position of axis. This function has to be selected with
. After the message “DNCO Data will be
cleared. continue?” It has to be confirmed with yes or no.
The DESIGNER sense the rack position of the function
modules (FM) DNSL-DS or DNSL-DR. 14 function mod-
ules are possible.
Every motion control has two position monitorings. In the
fields beside FM the increments number of the encoder
can be written.
Always if no function modes are selected and the axis
stop, DNSL-DS, DR record this position as the new moni-
tored position.
The monitored axis can oscillate lift and right but not more than these predetermined increments. If it decrease, the
virtual contact SS1 or SS2 in the wiring layer opens.
Notice: If position is monitored, no standstill monitoring is possible.