Chapter 4 Parameters
|
VFD-VL
4-6
Pr.
Explanation
Settings
Factory
Setting
VF
VFPG
SVC
FO
CPG
TQ
CPG
FO
CP
M
(MO3)
13: Overheat (Pr.06-14)
○ ○ ○ ○ ○ ○
14: Brake chopper signal
0
○ ○ ○ ○ ○ ○
15: Motor-controlled magnetic contactor output
0
○ ○ ○ ○ ○ ○
02-16 Multi-function Output 6
(MO4)
16: Slip error (oSL)
○ ○ ○ ○
○
17: Malfunction indication 1
○ ○ ○ ○ ○ ○
18:
Reserved
19: Brake chopper output error
○ ○ ○ ○ ○ ○
20: Warning output
○ ○ ○ ○ ○ ○
02-17 Multi-function Output 7
(MO5)
21: Over voltage warning
0
○ ○ ○ ○ ○ ○
22: Over-current stall prevention warning
0
○ ○ ○
02-18 Multi-function Output 8
(MO6)
23: Over-voltage stall prevention warning
○ ○ ○ ○ ○ ○
24: Operation mode indication (Pr.00-15
≠
0 and PU LED on
KPVL-CC01 is off)
○ ○ ○ ○ ○ ○
02-19 Multi-function Output 9
(MO7)
25: Forward command
0
○ ○ ○ ○ ○ ○
26: Reverse command
○ ○ ○ ○ ○ ○
02-20 Multi-function Output 10
(MO8)
27: Output when current >= Pr.02-33
0
○ ○ ○ ○ ○ ○
28: Output when current < Pr.02-33
○ ○ ○ ○ ○ ○
02-21 Multi-function Output 11
(MO9)
29: Output when frequency >= Pr.02-34
0
○ ○ ○ ○ ○ ○
30: Output when frequency < Pr.02-34
0
○ ○ ○ ○ ○ ○
02-22 Multi-function Output 12
(MO10)
31: Power generation direction and status verify
○ ○ ○ ○ ○ ○
32: Power generation direction
○ ○ ○ ○ ○ ○
33: Zero speed (actual output frequency)
○ ○ ○ ○
○
34: Zero speed with Stop (actual output frequency)
○ ○ ○ ○
○
35: Fault output option 1 (Pr.06-22)
○ ○ ○ ○ ○ ○
36: Fault output option 2 (Pr.06-23)
○ ○ ○ ○ ○ ○
37: Fault output option 3 (Pr.06-24)
○ ○ ○ ○ ○ ○
38: Fault output option 4 (Pr.06-25)
○ ○ ○ ○ ○ ○
39:
Reserved
40: Speed attained (including zero speed)
○ ○ ○ ○
○
41:
Reserved
02-23 Multi-output Direction
0 ~ 65535
0
○ ○ ○ ○ ○ ○
02-24
Serial Start Signal Selection 0: by FWD/REV
1: by Enable
0
○ ○ ○ ○
○
02-25 Desired Frequency Attained
1
0.00 ~ 400.00Hz
60.00/
50.00
○ ○ ○ ○
○
02-26 The Width of the Desired
Frequency Attained 1
0.00 ~ 400.00Hz
2.00
○ ○ ○ ○
○
02-27 Desired Frequency Attained
2
0.00 ~ 400.00Hz
60.00/
50.00
○ ○ ○ ○
○
02-28 The Width of the Desired
Frequency Attained 2
0.00 ~ 400.00Hz
2.00
○ ○ ○ ○
○
02-29
Brake Release Delay Time
when Elevator Starts
0.000~65.000 Sec
0.250
○ ○ ○ ○ ○ ○
02-30 Brake Engage Delay Time
when Elevator Stops
0.000~65.000 Sec
0.250
○ ○ ○ ○ ○ ○
02-31 Turn On Delay of Magnetic
Contactor between Drive
and Motor
0.000~65.000 Sec
0.200
○ ○ ○ ○ ○ ○
02-32 Turn Off Delay of Magnetic
Contactor between Drive
and Motor
0.000~65.000 Sec
0.200
○ ○ ○ ○ ○ ○
02-33 Output Current Level Setting
for External Terminals
0~100%
0
○ ○ ○ ○ ○ ○
02-34 Output Boundary for
External Terminals
0.00~+-400.00Hz (it is motor speed when using with PG)
0.00
○ ○ ○ ○ ○ ○
02-35 Detection Time of
Mechanical Brake
0.00~10.00 Sec
0.00
○ ○ ○ ○ ○ ○
02-36 Detection Time of Contactor 0.00~10.00 Sec
0.00
○ ○ ○ ○ ○ ○
02-37
Check Torque Output
Function
0: Enable
1: Disable
0
○ ○ ○ ○ ○ ○