Chapter 4 Parameters
|
VFD-VL
4-37
This parameter selects the frequency point for transition from acceleration/deceleration time 1
to acceleration/deceleration time 4.
The transition from acceleration/deceleration time 1 to acceleration/deceleration time 4, may
also be enabled by the external terminals (Pr. 02-01 to 02-08). The external terminal has
priority over Pr. 01-23.
Frequency
1st/4th Acceleration/Deceleration Switching
01-23
4th Acceleration Time
4th Deceleration
Time
1st Acceleration
Time
1st Deceleration
Time
1st/4th
Acceleration
/Deceleration
Freq.
01-24
S-curve for Acceleration Departure Time S1
01-25
S-curve for Acceleration Arrival Time S2
01-26
S-curve for Deceleration Departure Time S3
01-27
S-curve for Deceleration Arrival Time S4
01-30
S-curve for Deceleration Arrival Time S5
Control
mode
VF
VFPG
SVC
FOCPG FOCPM
Factory setting: 1.00
Settings
0.00~25.00
sec
01-29
Switch Frequency for S3/S4 Changes to S5
Control
mode
VF
VFPG
SVC
FOCPG
FOCP
M
Factory setting: 0.00
Settings
0.00~400.00Hz
It is used to give the smoothest transition between speed changes. The accel./decel. curve
can adjust the S-curve of the accel./decel. When it is enabled, the drive will have different
accel./decel. curve by the accel./decel. time.
The Actual Accel. Time = selected accel. Time + (Pr.01-24 + Pr.01-25)/2
The Actual Decel. Time = selected decel. Time + (Pr.01-26 + Pr.01-27 + Pr.01-30*2)/2
Pr.01-29 is used to set the switch frequency between S4 and S5 for smooth stop.
It is recommended to set this parameter to the leveling speed of elevator.