Chapter 3 Operation and Start Up
|
VFD-VL
3-9
Setting the parameters according to the motor type (PM or IM)
Motor Auto-tuning: When the Source of the Operation Command is set to digital
keypad (Pr.00-15=2, refer to step 1)
Control method: Please set Pr.00-09 to 8.
Pr.00-09
Control Method
0: V/f Control
1: V/f C Encoder (VFPG)
2: Sensorless vector control (SVC)
3: FOC vector c Encoder (FOCPG)
4: Torque c Encoder (TQCPG)
8: FOC PM control (FOCPM)
NOTE: Setting parameter by the motor type (PM or IM).
Inputting the nameplate information on the motor into Pr.01-00~01-02
Pr.01-00
Maximum Output Frequency
10.00~120.00Hz
Pr.01-01
1st Output Frequency Setting 1
(base frequency/motor rated
frequency)
0.00~120.00Hz
Pr.01-02
1st Output Voltage Setting 1
(base voltage/motor rated
voltage)
230V: 0.1V~255.0V
460V: 0.1V~510.0V
IM
Motor Auto-tuning: When the Source of the Operation Command is set to digital
keypad (Pr.00-15=2, refer to step 1) and setting Pr.05-00=2
Pr.05-00
Motor Auto tuning
0: No function
1: Rolling test (Rs, Rr, Lm, Lx, no-load current)
2: Static Test
NOTE 1: It doesn’t need to release the brake in this auto tuning operation. Please make sure that
the electromagnetic valve is ON when it is used between the AC motor drive and motor. When
Pr.05-00 is set to 2, no-load current of motor must be entered into Pr.05-05. The warning message
“Auto tuning” will be displayed on the digital keypad during tuning until it is finished. Then, the
measure result will be saved into Pr.05-06~Pr.05-09.
NOTE 2: It needs to finish motor auto tuning before measuring the angle between magnetic pole
and PG origin.
Pr.05-01
Full-load Current of Motor
(40~120%)*00-01 Amps