Chapter 4 Parameters
|
VFD-VL
4-26
Terminal
MI8 MI7 MI6
MI5
MI4
MI3
MI2 MI1
REV
FWD
Status
0 0 1 0 0 0 0 1 1 0
0: OFF, 1: ON
MI1: Pr.02-01 is set to 1 (multi-step speed command 1)
MI8: Pr.02-08 is set to 8 (the 1st, 2nd acceleration/deceleration time selection)
If REV, MI1 and MI8 are ON, the value is 0000 0000 1000 0110
2
in binary and 0086H in HEX.
At the meanwhile, if Pr.00-04 is set to “14” or “17”, it will display “0086” with LED U is ON on
the keypad KPVL-CC01. The setting 14 is the status of digital input and the setting 17 is the
corresponding CPU pin status of digital input. User can set to 14 to monitor digital input status
and then set to 17 to check if the wire is normal.
D
U:
O
O
E
O
N/
E
FF S
t
t a
E
S
E
E
EE
0
EE
1
0 0
E
E
E
E
Terminal MO10 MO9 MO8 MO7 MO6 MO5 MO4 MO3 MO2 MO1 MRA
RA MO10
Status
0 0 0 0 1 0 0 0 0 1 1 0 0
RA: Pr.02-11 is set to 9 (Drive ready).
After applying the power to the AC motor drive, if there is no other abnormal status, the
contact will be ON. At the meanwhile, if Pr.00-04 is set to 15 or 18, it will display 0001 with
LED U is ON on the keypad. The setting 15 is the status of digital output and the setting 18 is
the corresponding CPU pin status of digital output. User can set 15 to monitor the digital
output status and then set to 18 to check if the wire if normal.
00-05
User Defined Coefficient K
Control
mode
VF
VFPG
SVC
FOCPG TQCPG FOCPM
Factory setting: 0
Settings
Digit 4: decimal point number (0 to 3)
Digit 0-3: 40 to 9999
It is used digital setting method
Digital 4: decimal point number (0: no decimal point, 1: 1 decimal point and so on.)
Digit 0-3: 40 to 9999 (the corresponding value for the max. frequency).