A-1
Appendix A Specifications
There are 230V and 460V models for customers to choose by their requirement.
Voltage Class
230V Class
Model Number VFD-XXXVL
055 075 110 150 185 220 300 370
Max. Applicable Motor Output (kW)
5.5
7.5
11
15
18.5
22
30
37
Max.
Applicable
Motor
Output
(hp)
7.5 10 15 20 25 30 40 50
Rated Output Capacity (kVA)
9.5
12.5 19 25 29 34 46 55
Rated Output Current for
General Purposes (A)
21.9 27.1 41.1 53 70 79 120 146
**Rated Output Current for
Elevators (A)
25 31 47 60 80 90 150 183
Maximum Output Voltage (V)
3-Phase Proportional to Input Voltage
Output Frequency (Hz)
0.00~120.00 Hz
Output Rating
Carrier Frequency (kHz)
12kHz 9kHz
6kHz
Rated Input Current (A)
25
31
47
60
80
90
106
126
Rated Voltage/Frequency
3-phase
200-240V, 50/60Hz
Voltage Tolerance
±
10%(180~264 V)
Input R
a
ting
Frequency Tolerance
±
5%(47~63 Hz)
Cooling Method
Fan Cooled
Weight
(kg)
8 10 10 13 13 13 36 36
Voltage Class
460V Class
Model Number VFD-XXXVL 055
075
110
150
185
220 300
370
450
550
750
Max. Applicable Motor Output (kW) 5.5
7.5
11
15
18.5
22
30
37
45
55
75
Max. Applicable Motor Output (hp)
7.5
10
15
20
25
30
40
50
60
75
100
Rated Output Capacity (kVA)
9.9
13.7
18
24
29 34 46
56
69
80
100
Rated Output Current for
General Purposes (A)
12.3
15.8
21
27
34 41 60
73
91
110
150
**Rated Output Current for
Elevators (A)
14
18
24
31
39 47 75
91
113
138
188
Maximum Output Voltage (V)
3-phase Proportional to Input Voltage
Output Frequency (Hz)
0.00~120.00 Hz
Output Rating
Carrier Frequency (kHz)
15kHz 9kHz
6kHz
Rated Input Current (A)
14
18
24
31
39
47
56
67
87
101
122
Rated Voltage
3-phase 380 to 480 V, 50/60Hz
Voltage Tolerance
±
10%(342~528 V)
Input R
a
ting
Frequency Tolerance
±
5%(47~63 Hz)
Cooling Method
Fan Cooled
Weight (kg)
8
10
10
13
13
13
36
36
36
50
50
Call 1(800)985-6929 for Sales
deltaacdrives.com
Call 1(800)985-6929 for Sales
deltaacdrives.com