Chapter 4 Parameters
|
VFD-VL
4-4
4.1.2 Group 1 Basic Parameters
Pr.
Explanation
Settings
Factory
Setting
VF
VFPG
SVC
FO
CPG
TQ
CPG
FO
CP
M
01-00 Maximum
Output
Frequency 10.00~400.00Hz
60.00/
50.00
○ ○ ○ ○ ○ ○
01-01
1st Output Frequency
Setting 1
0.00~400.00Hz
60.00/
50.00
○ ○ ○ ○ ○ ○
01-02 1st Output Voltage Setting 1
230V: 0.1V~255.0V
460V: 0.1V~510.0V
220.0
440.0
○ ○ ○ ○ ○ ○
01-03
2nd Output Frequency
Setting 1
0.00~400.00Hz 0.50
○ ○
01-04
2nd Output Voltage Setting
1
230V: 0.1V~255.0V
460V: 0.1V~510.0V
5.0
10.0
○ ○
01-05
3rd Output Frequency
Setting 1
0.00~400.00Hz 0.50
○ ○
01-06 3rd Output Voltage Setting 1
230V: 0.1V~255.0V
460V: 0.1V~510.0V
5.0
10.0
○ ○
01-07
4th Output Frequency
Setting 1
0.00~400.00Hz 0.00
○ ○ ○ ○ ○
01-08 4th Output Voltage Setting 1
230V: 0.1V~255.0V
460V: 0.1V~510.0V
0.0
0.0
○ ○
01-09 Start
Frequency
0.00~400.00Hz 0.50
○ ○ ○ ○
01-10
Output Frequency Upper
Limit
0.00~400.00Hz
120.00
○ ○ ○ ○
○
01-11
Output Frequency Lower
Limit
0.00~400.00Hz
0.00
○ ○ ○ ○
○
01-12 Accel Time 1
0.00~600.00 sec
3.00
○ ○ ○ ○
○
01-13 Decel Time 1
0.00~600.00 sec
2.00
○ ○ ○ ○
○
01-14 Accel Time 2
0.00~600.00 sec
3.00
○ ○ ○ ○
○
01-15 Decel Time 2
0.00~600.00 sec
2.00
○ ○ ○ ○
○
01-16 Accel Time 3
0.00~600.00 sec
3.00
○ ○ ○ ○
○
01-17 Decel Time 3
0.00~600.00 sec
2.00
○ ○ ○ ○
○
01-18 Accel Time 4
0.00~600.00 sec
3.00
○ ○ ○ ○
○
01-19 Decel Time 4
0.00~600.00 sec
2.00
○ ○ ○ ○
○
01-20 JOG Acceleration Time
0.00~600.00 sec
1.00
○ ○ ○ ○
○
01-21 JOG Deceleration Time
0.00~600.00 sec
1.00
○ ○ ○ ○
○
01-22 JOG Frequency
0.00~400.00Hz 6.00
○ ○ ○ ○ ○ ○
01-23
Switch Frequency between
1st/4th Accel/decel
0.00~400.00Hz 0.00
○ ○ ○ ○
○
01-24
S-curve for Acceleration
Departure Time S1
0.00~25.00 sec
1.00
○ ○ ○ ○
○
01-25
S-curve for Acceleration
Arrival Time S2
0.00~25.00 sec
1.00
○ ○ ○ ○
○
01-26
S-curve for Deceleration
Departure Time S3
0.00~25.00 sec
1.00
○ ○ ○ ○
○
01-27
S-curve for Deceleration
Arrival Time S4
0.00~25.00 sec
1.00
○ ○ ○ ○
○
01-28
Mode Selection when
Frequency < Fmin
0: Output waiting
1: Zero-speed operation
2: Fmin (4th output frequency setting)
0
○ ○ ○
01-29
Switch Frequency for S3/S4
Changes to S5
0.00~400.00Hz 0.00
○ ○ ○ ○
○
01-30
S-curve for Deceleration
Arrival Time S5
0.00~25.00 sec
1.00
○ ○ ○ ○
○
01-31
Deceleration Time when
Operating without RUN
Command
0.00~60.00 sec
2.00
○ ○ ○ ○
○
Call 1(800)985-6929 for Sales
deltaacdrives.com
Call 1(800)985-6929 for Sales
deltaacdrives.com