Chapter 4 Parameters
|
VFD-VL
4-2
4.1 Summary of Parameter Settings
: The parameter can be set during operation.
4.1.1 Group 0 System Parameters
Pr.
Explanation
Settings
Factory
Setting
VF
VFPG
SVC
FO
CPG
TQ
CPG
FO
CP
M
00-00
Identity Code of the AC
motor drive
Read-only
#
○ ○ ○ ○ ○ ○
00-01
Rated Current Display of the
AC motor drive
Read-only #
○ ○ ○ ○ ○ ○
00-02
Parameter Reset
0: No function
1: Read only
8: Keypad lock
9: All parameters are reset to factory settings (50Hz,
220V/380V)
10: All parameters are reset to factory settings (60Hz,
220V/440V)
0
○ ○ ○ ○ ○ ○
00-03 Start-up Display Selection
0: Display the frequency command value (LED F)
1: Display the actual output frequency (LED H)
2: DC BUS voltage
3: Display the output current (A)
4: Output voltage
5: Multifunction display, see Pr.00-04
0
○ ○ ○ ○ ○ ○
00-04
Content of Multi Function
Display
0: Display output current (A)
1: Reserved
2: Display output frequency (H)
3: Display DC-BUS voltage (U)
4: Display output voltage (E)
5: Output power factor angle (n)
6: Display output power kW(P)
7: Display actual motor speed in rpm(r
)
8: Display estimate output torque %
9: Display PG position (G)
10: Display the electrical angle of drive output
11: Display AUI1 % (1.)
12: Display ACI % (2.)
13: Display AUI2 % (3.)
14: Display the temperature of heat sink (
°
C)
15: Display the temperature of IGBT
°
C (T.)
16: The status of digital input ON/OFF (i)
17: The status of digital output ON/OFF (o)
18: Multi-step speed (S)
19: The corresponding CPU pin status of digital input (i.)
20: The corresponding CPU pin status of digital output (o.)
21-23: Reserved
24: Output AC voltage when malfunction (8)
25: Output DC voltage when malfunction (8.)
26: Motor frequency when malfunction (h)
27: Output current when malfunction (4)
28: Output frequency when malfunction (h.)
29: Frequency command when malfunction
30: Output power when malfunction
31: Output torque when malfunction
32: Input terminal status when malfunction
33: Output terminal status when malfunction
34: Drive status when malfunction
0
○ ○ ○ ○ ○ ○
00-05 User-Defined Coefficient K
Digit 4: decimal point number (0 to 3)
Digit 0-3: 40 to 9999
0
○ ○ ○ ○ ○ ○
00-06
Software Version
Read-only #.#
○ ○ ○ ○ ○ ○
00-07 Password Input
1 to 9998 and 10000 to 65535
0 to 2: times of wrong password
0
○ ○ ○ ○ ○ ○
00-08 Password Set
1 to 9998 and 10000 to 65535
0: No password set or successful input in Pr.00-07
1: Password has been set
0
○ ○ ○ ○ ○ ○
00-09
Control Method
0: V/f Control
1: V/f C Encoder (VFPG)
2: Sensorless vector control (SVC)
3: FOC vector c Encoder (FOCPG)
0
○ ○ ○ ○ ○ ○