Chapter 4 Parameters
|
VFD-VL
4-63
4.
The rated speed can’t be larger or equal to 120f/p. (f: output frequency Pr.01-01, p: Number of
Motor Poles Pr.05-04)
5.
After the tuning, user needs to activate the drive again to make it operate if the source
command of Auto-tuning comes from external terminal,
05-01
Full-load Current of Motor
Control
mode
VF VFPG SVC
FOCPG TQCPG
Factory setting: #.##
Settings
(40 to 120%)*Pr.00-01 Amps
This value should be set according to the rated frequency of the motor as indicated on the
motor nameplate. The factory setting is 90% X rated current.
Example: if the rated current for 7.5hp (5.5kW) models is 25A and the factory setting is 22.5A.
In this way, the current range will be from 10A (25*40%) to 30A (25*120%).
05-02
Rated Power of Motor
Control
mode
SVC
FOCPG
TQCPG
Factory setting: #.##
Settings
0.00 to 655.35 kW
Factory Setting: #.##
It is used to set rated power of the motor. The factory setting is the power of the drive.
05-03
Rated Speed of Motor (rpm)
Control
mode
VFPG
SVC
FOCPG TQCPG
Factory setting: 1710
Settings
0 to 65535 rpm
It is used to set the rated speed of the motor and need to set according to the value indicated
on the motor nameplate.
05-04
Number of Motor Poles
Control
mode
VF
VFPG
SVC
FOCPG TQCPG
Factory setting: 4
Settings
2 to 48
It is used to set the number of motor poles (must be an even number).
05-05
No-load Current of Motor
Control
mode
VFPG
SVC
FOCPG TQCPG
Factory setting: #.##
Settings
0 to 100%
The factory setting is 40% X rated current.