Chapter 4 Parameters
|
VFD-VL
4-71
The parameter is set by the output frequency, current and operation time of the drive for
activating the I
2
t electronic thermal protection function. The function will be activated for the
150% * setting current for the setting of Pr.06-13.
1
2
3
4
5
60Hz
0
50
100
150
200
Operation
time( min)
Load
fac tor (%)
06-14
Heat Sink Over-heat (OH) Warning
Control
mode
VF
VFPG
SVC
FOCPG TQCPG FOCPM
Factory setting: 85.0
Settings
0.0 to 110.0
o
C
06-15
Stall Prevention Limit Level
Control
mode
VF
VFPG
SVC
Factory setting: 50
Settings
0 to 100% (refer to Pr.06-02, Pr.06-03)
When the operating frequency is larger than Pr.01-01, Pr06-02=150%, Pr. 06-03=100% and Pr.
06-15=80%:
Stall Prevention Level during acceleration
=
06-02x06-15=150x80%=120%.
Stall Prevention Level at constant speed
=
06-03x06-15=100x80%=80%.
06-02
06-15
01-01
01-01
x06-02
Stall Prevention Level
output frequency
frequency