Chapter 4 Parameters
|
VFD-VL
4-114
4.2.12 Group 11 Advanced Parameters
11-00
System Control
Control
mode
FOCPG
FOCPM
Factory
Setting:
0
Settings
Bit 0=0
No function
Bit 0=1
ASR Auto tuning, PDFF enable
Bit 7=0
No function
Bit 7=1
When position control is enabled, it doesn’t need to set Pr.07-02
(DC Brake Current Level)
Bit 15=0
when power is applied, it will detect the position of magnetic pole
again
Bit 15=1
when power is applied, it will start from the magnetic pole
position of previous power failure
Bit 0=1: PDFF function is enabled and system will generate an ASR setting, Pr. 10-11~10-16
will be invalid and Pr.11-09 to 11-10 will be valid.
YES
NO
Setting auto gain adjustment
Pr.11-00=1
Adjust Pr.11- 06, 11-07 and 11-08
separately by s peed response
Adjust by r equirement
Pr.11-09, Pr. 11-10 (PDFF function)
Adjust by requir ement Pr.10-17
(A SR1/ASR2 s wi tc h frequency)
Pr.10- 20: Zero speed/ASR1 width adjustment
Pr.10- 21: ASR1/ASR2 width adjustment
Adjust by requir ement Pr.07-25~28 (torque li mit)
Adjust gain value by manual
Pr.11-00=0 ( fac tor y s etting)
Adjust Pr.10-11, 10-12, 10- 13,
10-14, 10-15 and 10-16
separately by s peed response
Adjust by r equirement
Pr.10- 18 (for general,
no need to adjus t)
When Pr.11-00
is set B it 0=1