Chapter 4 Parameters
|
VFD-VL
4-36
01-00
01-13,15,17,19
01-12,14,16,18
Frequency
Time
Max. Output
Frequency
Frequency
Setting
accel. time
decel. time
Accel./Decel. Time
01-22
JOG Frequency
Control
mode
VF
VFPG
SVC
FOCPG TQCPG FOCPM
Factory
setting:
6.00
Settings
0.00~400.00Hz
Both external terminal JOG and key “JOG” on the keypad can be used. When the jog
command is ON, the AC motor drive will accelerate from 0Hz to jog frequency (Pr.01-22).
When the jog command is OFF, the AC motor drive will decelerate from Jog Frequency to zero.
The used Accel./Decel. time is set by the Jog Accel./Decel. time (Pr.01-20, Pr.01-21).
The JOG command can’t be executed when the AC motor drive is running. In the same way,
when the JOG command is executing, other operation commands are invalid except
forward/reverse commands and STOP key on the digital keypad.
F requenc y
Time
01-22
JO G frequency
01-07
4th output
frequency
setting
01-20
01-21
JO G ac celeration time
JO G dec el er ation time
JO G ac cel./dec el . time
01-23
Switch Frequency between 1st/4th Accel/decel
Control
mode
VF
VFPG
SVC
FOCPG FOCPM
Factory setting: 0.00