Chapter 3 Operation and Start Up
|
VFD-VL
3-16
Pr.10-22
Operation Time of
Zero Speed
0.000~65.535sec
Pr.10-23
Filter Time of Zero
Speed
0.000~65.535sec
Pr.10-24
Time for Zero Speed
Execution
0: after the brake release set in Pr.02-29
1: after the brake signal input (Pr.02-01~02-08 is set to
42)
Pr.02-29
Brake Release Delay
Time when Elevator
Starts
0.000~65.000 Sec
NOTE: When Pr.10-24=0, the zero speed control needs to be used with Pr.02-29. (refer to
the explanations in Pr.02-32)
Function of the preload input
Please connect the signal of the preload signal to the external terminal of the AC motor
drive (AUI1) and setting Pr.03-00=11, 07-19=1, 03-03, 03-06 and 03-09.
Pr.03-00
Analog Input 1 (AUI1)
0: No function
1: Frequency command (torque limit under TQR control
mode)
2: Torque command (torque limit under speed mode)
3: Torque compensation command
4-5: Reserved
6: P.T.C. thermistor input value
7: Positive torque limit
8: Negative torque limit
9: Regenerative torque limit
10: Positive/negative torque limit
Pr.07-19
Source of Torque
Offset
0: Disable
1: Analog input (Pr.03-00)
2: Torque offset setting (Pr.07-20)
3: Control by external terminal (by Pr.07-21 to Pr.07-23)