Chapter 4 Parameters
|
VFD-VL
4-23
00-02
Parameter Reset
Control
mode
VF
VFPG
SVC
FOCPG TQCPG FOCPM
Factory setting: 0
Settings
0
No
Function
1
Read
Only
8
Keypad
Lock
9 All parameters are reset to factory settings (50Hz, 220V/380V)
10 All parameters are reset to factory settings (60Hz, 220V/440V)
When it is set to 1, all parameters are read only except Pr.00-00~00-07 and it can be used
with password setting for password protection.
This parameter allows the user to reset all parameters to the factory settings except the fault
records (Pr.06-16 ~ Pr.06-21).
50Hz: Pr.01-01 is set to 50Hz and Pr.01-02 is set to 230V or 400V.
60Hz: Pr.01-01 is set to 60Hz and Pr.01-02 is set to 230Vor 460V.
When
Pr.00-02=08,
the KPVL-CC01 keypad is locked and only Pr.00-02 can be set. To unlock
the keypad, set Pr.00-02=00.
When Pr.00-02 is set to 1, Pr.00-02 setting should be set to 0 before setting to other setting.
00-03
Start-up Display Selection
Control
mode
VF
VFPG
SVC
FOCPG TQCPG FOCPM
Factory setting: 0
Settings 0
Display the frequency command value. (LED F)
1
Display the actual output frequency (LED H)
2
DC BUS voltage
3
Display the output current (A)
4
Output
voltage
5
Multifunction display, see Pr.00-04
This parameter determines the start-up display page after power is applied to the drive.
00-04
Content of Multi-Function Display
Control
mode
VF
VFPG
SVC
FOCPG TQCPG FOCPM
Factory setting: 0
Settings
0 Display the output current in A supplied to the motor
O
U:
p
ut
E
ut
r
Cu r
t
en
E
S
E
E
EE
0
EE
A
. 0 m
E
ps
1
Reserved