AL060 Absolute position is lost
Checking method
and corrective action
4.
Connect or correct the wiring so that the battery power is supplied to the
encoder and then re-establish the absolute origin coordinates.
(a)
Check the encoder wiring.
(b)
Check the connection between the battery box and servo drive.
How to clear the
alarm?
Connect or correct the wiring so that the battery power is supplied to the encoder
and then re-establish the absolute origin coordinates. Refer to Chapter 10 for more
information on the absolute servo system.
AL061 Encoder undervoltage
Trigger condition
and cause
Condition: voltage level of the absolute encoder battery is lower than the allowable
value (3.1V).
Cause: voltage level of the battery is too low
Checking method
and corrective action
1.
Check the panel to see if the battery voltage is below 3.1V.
2.
Measure the battery voltage to see if it is below 3.1V.
If the voltage is too low, replace the battery when the main power is on.
How to clear the
alarm?
The alarm is cleared automatically.
AL062 Number of turns for the absolute encoder overflows
Trigger condition
and cause
Condition: the number of turns for the absolute encoder exceeds the range:
-32768 to +32767.
Cause: motor’s rotation cycle exceeds the allowable range.
Checking method
and corrective action
Check if the motor’s number of turns while operating is within the range between
-32768 and +32767. If not, re-establish the absolute origin coordinates.
How to clear the
alarm?
Cycle power on the servo drive.
AL067 Encoder temperature warning
Trigger condition
and cause
Condition: the encoder temperature is over 85˚C (warning level), but still under
100˚C, which is within the protective range.
Cause: encoder temperature warning (85˚C - 100˚C).
Checking method
and corrective action
Set P0.002 to -124 d and check if the encoder temperature is identical to the motor
temperature. If the encoder temperature is too high, improve the heat dissipation to
lower the temperature. If the temperature difference between the encoder and
motor is over 30˚C, send the motor back to the distributor.
How to clear the
alarm?
Cycle power on the servo drive.
Summary of Contents for ASDA-A3 Series
Page 15: ... This page is intentionally left blank ...
Page 89: ...Wiring ASDA A3 3 38 3 Pin assignment for the CN1 quick connector J2 and J1 ...
Page 91: ...Wiring ASDA A3 3 40 3 Wiring for CN1 quick connector and installation Installation ...
Page 373: ...Motion Control ASDA A3 7 176 7 This page is intentionally left blank ...
Page 605: ...Parameters ASDA A3 8 232 8 This page is intentionally left blank ...
Page 623: ...MODBUS Communication ASDA A3 9 18 9 This page is intentionally left blank ...
Page 645: ...Absolute System ASDA A3 10 22 10 This page is intentionally left blank ...
Page 661: ...Linear Motor ASDA A3 11 16 11 This page is intentionally left blank ...
Page 793: ...Troubleshooting ASDA A3 13 48 13 This page is intentionally left blank ...
Page 819: ...Specifications ASDA A3 A 26 A This page is intentionally left blank ...
Page 841: ...Accessories ASDA A3 B 22 B This page is intentionally left blank ...