1.
Disconnect from mains and wait until
the display turns off.
2a. Press [Status] - [Main Menu] - [OK]
at the same time while power up for
LCP 102, Graphical Display
2b. Press [Menu] while power up for LCP
101, Numerical Display
3.
Release the keys after 5 s.
4.
The frequency converter is now pro-
grammed according to default set-
tings.
This procedure initialises all except:
15-00
Operating Hours
15-03
Power-up's
15-04
Over temp's
15-05
Over volt's
NB!
When you carry out manual initialisation, you also reset serial communication, RFI
filter settings (par. 14-50) and fault log settings.
Removes parameters selected in
Personal Menu
.
NB!
After initialization and power cycling, the display will not show any information until
after a couple of minutes.