0-39 Display Text 3
Option:
Function:
In this parameter it is possible to write an individual text string
for display in the LCP or to be read via serial communication. If
to be displayed permanently select Display Text 3 in par. 0-20,
0-21, 0-22, 0-23 or 0-24,
Display Line XXX
. Use the
▲
or
▼
but-
tons on the LCP to change a character. Use the
◀
and
▶
buttons
to move the cursor. When a character is highlighted by the cur-
sor, this character can be changed. A character can be inserted
by placing the cursor between two characters and pressing
▲
or
▼
.
2.2.6. LCP Keypad, 0-4*
Enable, disable and password protect individual keys on the LCP keypad.
0-40 [Hand on] Key on LCP
Option:
Function:
[0]
Disabled
No function
[1]
*
Enabled
[Hand on] Key enabled
[2]
Password
Avoid unauthorized start in Hand mode. If par. 0-40 is included
in the Quick Menu, then define the password in par. 0-65
Quick
Menu Password
. Otherwise define the password in par. 0-60
Main Menu Password.
0-41 [Off] Key on LCP
Option:
Function:
[0]
Disabled
No function
[1]
*
Enabled
[Off] Key is enabled
[2]
Password
Avoid unauthorized stop. If par. 0-41 is included in the Quick
Menu, then define the password in par. 0-65
Quick Menu Pass-
word
. Otherwise define the password in par. 0-60 Main Menu
Password.
0-42 [Auto on] Key on LCP
Option:
Function:
[0]
Disabled
No function
[1]
*
Enabled
[Auto on] Key is enabled
[2]
Password
Avoid unauthorized start in Auto mode. If par. 0-42 is included
in the Quick Menu, then define the password in par. 0-65
Quick
Menu Password
. Otherwise define the password in par. 0-60
Main Menu Password.
VLT
®
AQUA Drive Programming Guide
2. Parameter Description
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
39