maximum signal value, i.e. 0 mA (or 0 Hz) is desired at 25% of
the maximum output value and 25% is programmed. The value
can never be higher than the corresponding setting in par. 6-62
if value is below 100%.
This parameter is active when option module MCB 101 is moun-
ted in the frequency converter.
6-62 Term. X30/8 Output Max Scale
Range:
Function:
100%
*
[0.00 - 200 %]
Scales the maximum output of the selected analog signal on
terminal X30/8. Scale the value to the desired maximum value
of the current signal output. Scale the output to give a lower
current than 20 mA at full scale or 20 mA at an output below
100% of the maximum signal value. If 20 mA is the desired
output current at a value between 0 - 100% of the ful-scale
output, program the percentage value in the parameter, i.e.
50% = 20 mA. If a current between 4 and 20 mA is desired at
maximum output (100%), calculate the percentage value as
follows:
20
mA
/
desired maximum current
× 100 %
i.e. 10 mA : 20 mA
10
mA × 100 % = 200 %
6-63 Terminal X30/8 Output Bus Control
Range:
Function:
0 %
*
[0 – 100 %]
Contains the value to apply to the output terminal, when it is
configured as [Bus Controlled].
6-64 Terminal X30/8 Output Timeout Preset
Range:
Function:
0 %
*
[0 – 100 %]
Contains the value to apply to the output terminal, when it is
configured as [Bus Controlled Timeout] and timeout is detected.