25-44 Staging Speed [RPM]
Option:
Function:
0 N/A
Readout of the below calculated value for Staging Speed When
adding a fixed speed pump, in order to prevent an overshoot of
pressure, the variable speed pump ramps down to a lower
speed. When the variable speed pump reaches the “Staging
Speed” the fixed speed pump is staged on. Staging Speed cal-
culation is based on
Staging Threshold
, par. 25-42, and
Motor
Speed High Limit [RPM]
, par. 4-13.
Staging Speed is calculated with the following formula:
η
STAGE
=
η
HIGH
η
STAGE %
100
where n
HIGH
is Motor Speed High Limit and n
STAGE100%
is the val-
ue of Staging Threshold.
25-45 Staging Speed [Hz]
Option:
Function:
0 N/A
Readout of the below calculated value for Staging Speed When
adding a fixed speed pump, in order to prevent an overshoot of
pressure, the variable speed pump ramps down to a lower
speed. When the variable speed pump reaches the “Staging
Speed” the fixed speed pump is staged on. Staging Speed cal-
culation is based on
Staging Threshold
, par. 25-42, and
Motor
Speed High Limit [Hz]
, par. 4-14.
Staging Speed is calculated with the following formula:
η
STAGE
=
η
HIGH
η
STAGE %
100
where n
HIGH
is Motor Speed
High Limit and n
STAGE100%
is the value of Staging Threshold.
25-46 Destaging Speed [RPM]
Option:
Function:
0 N/A
Readout of the below calculated value for Destaging Speed.
When removing a fixed speed pump, in order to prevent an un-
dershoot of pressure, the variable speed pump ramps up to a
higher speed. When the variable speed pump reaches the “De-
staging Speed” the fixed speed pump is destaged. Destaging
Speed is calculated based on
Destaging Threshold
, par. 25-43,
and
Motor Speed High Limit
, par. 4-13.
Destaging Speed is calculated with the following formula:
2. Parameter Description
VLT
®
AQUA Drive Programming Guide
236