6-30 Term. X30/11 Low Voltage
Range:
Function:
0.07 V
*
[0 - par. 6-31]
Sets the analog input scaling value to correspond to the low
reference/feedback value (set in par. 6-34).
6-31 Term. X30/11 High Voltage
Range:
Function:
10.0 V
*
[Par. 6-30 to 10.0 V] Sets the analog input scaling value to correspond to the high
reference/feedback value (set in par. 6-35).
6-34 Term. X30/11 Low Ref./Feedb. Value
Range:
Function:
0.000
Unit
*
[1000000.000 to par.
6-35]
Sets the analog input scaling value to correspond to the low
voltage value (set in par. 6-30).
6-35 Term. X30/11 High Ref./Feedb. Value
Range:
Function:
1500.00
0 Unit
[Par. 6-34 to
1000000.000]
Sets the analog input scaling value to correspond to the high
voltage value (set in par. 6-31).
6-36 Term. X30/11 Filter Time Constant
Range:
Function:
0.001s
*
[0.001 - 10.000 s]
A 1
st
order digital low pass filter time constant for suppressing
electrical noise on terminal X30/11.
Par. 6-36 cannot be changed while the motor is running.
6-37 Term. X30/11 Live Zero
Option:
Function:
This parameter makes it possible to disable the Live Zero mon-
itoring. E.g. to be used if the analog outputs are used as part of
a decentral I/O system (e.g. when not part of any frequency
converter related control functions, but feeding an external con-
trol system with data)
[0]
*
Disabled
[1]
Enabled
2.8.7. 6-4* Analog Input 4 (MCB 101)
Parameter group for configuring the scale and limits for analog input 4 (X30/12) placed on option
module MCB 101.
6-40 Term. X30/12 Low Voltage
Range:
Function:
0.7 V
*
[0 to par. 6-41]
Sets the analog input scaling value to correspond to the low
reference/feedback value set in par. 6-44.
VLT
®
AQUA Drive Programming Guide
2. Parameter Description
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
101
2