Use par. 0-51
Set-up copy
to copy a set-up to one or all other
set-ups. To avoid conflicting settings of the same parameter
within two different set-ups, link the set-ups together using par.
0-12 This Set-up Linked to
. Stop the frequency converter before
switching between set-ups where parameters marked ‘not
changeable during operation’ have different values.
Parameters which are ‘not changeable during operation’ are
marked FALSE in the parameter lists in the section
Parameter
Lists
[0]
Factory setup
Cannot be changed. It contains the Danfoss data set, and can
be used as a data source when returning the other set-ups to a
known state.
[1]
*
Set-up 1
Set-up 1
[1] to
Set-up 4
[4] are the four separate parameter
set-ups within which all parameters can be programmed.
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
Multi set-up
Is used for remote selection of set-ups using digital inputs and
the serial communication port. This set-up uses the settings
from par. 0-12 This option linked to.
0-11 Programming Set-up
Option:
Function:
Select the set-up to be edited (i.e. programmed) during opera-
tion; either the active set-up or one of the inactive set-ups. The
set-up number being edited is displayed in the LCP in (brackets).
[0]
Factory setup
cannot be edited but it is useful as a data source to return the
other set-ups to a known state.
[1]
Set-up 1
Set-up 1
[1] to
Set-up 4
[4] can be edited freely during opera-
tion, independently of the active set-up.
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
*
Active Set-up
(i.e. the set-up in which the frequency converter is operating)
can also be edited during operation. Editing parameters in the
chosen setup would normally be done from the LCP but it is also
possible from any of the serial communication ports.
0-12 This Set-up Linked to
Option:
Function:
This parameter only needs to be programmed if changing set-
ups is required whilst the motor is running. It ensures that
parameters which are "not changeable during operation" have
the same setting in all relevant set-ups.
To enable conflict-free changes from one set-up to another
whilst the frequency converter is running, link set-ups contain-
2. Parameter Description
VLT
®
AQUA Drive Programming Guide
28
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
2