Logic AND
Activates Start command via the fieldbus/serial communication
port, AND additionally via one of the digital inputs.
[3]
*
Logic OR
Activates Start command via the fieldbus/serial communication
port OR via one of the digital inputs.
Select control of the frequency converter start function via the
terminals (digital input) and/or via the fieldbus.
NB!
This parameter is active only when
par. 8-01 Control Site
is set to [0]
Digital and
control word
.
8-54 Reversing Select
Option:
Function:
[0]
*
Digital input
[1]
Bus
Activates Reverse command via the serial communication port
or fieldbus option.
[2]
Logic AND
Activates Reverse command via the fieldbus/serial communica-
tion port, AND additionally via one of the digital inputs.
[3]
Logic OR
Activates Reverse command via the fieldbus/serial communica-
tion port OR via one of the digital inputs.
Select control of the frequency converter reverse function via
the terminals (digital input) and/or via the fieldbus.
NB!
This parameter is active only when
par. 8-01 Control Site
is set to [0]
Digital and
control word
.
8-55 Set-up Select
Option:
Function:
[0]
Digital input
[1]
Bus
Activates the set-up selection via the serial communication port
or fieldbus option.
[2]
Logic AND
Activates the set-up selection via the fieldbus/serial communi-
cation port, AND additionally via one of the digital inputs.
[3]
*
Logic OR
Activate the set-up selection via the fieldbus/serial communica-
tion port OR via one of the digital inputs.
Select control of the frequency converter set-up selection via
the terminals (digital input) and/or via the fieldbus.
NB!
This parameter is active only when
par. 8-01 Control Site
is set to [0]
Digital and
control word
.