16-15 Frequency [%]
Range:
Function:
0.00%
*
[-100.00 - 100.00 %] View a two-byte word reporting the actual motor frequency
(without resonance dampening) as a percentage (scale
0000-4000 Hex) of par. 4-19
Max. Output Frequency
. Set par.
9-16 index 1 to send it with the Status Word instead of the MAV.
16-16 Torque [Nm]
Range:
Function:
0.0Nm
*
[-3000.0 - 3000.0
Nm]
View the torque value with sign, applied to the motor shaft.
Linearity is not exact between 110% motor current and torque
in relation to the rated torque. Some motors supply more than
160% torque. Consequently, the min. value and the max. value
will depend on the max. motor current as well as the motor
used. The value is filtered, and thus approx. 1.3 seconds may
pass from when an input changes value to when the data read-
out values change.
16-17 Speed [RPM]
Range:
Function:
0 RPM
*
[-30000 - 30000 RPM] View the actual motor RPM.
16-18 Motor Thermal
Range:
Function:
0 %
*
[0 - 100 %]
View the calculated thermal load on the motor. The cut-out limit
is 100%. The basis for calculation is the ETR function selected
in par.1-90.
16-22 Torque
Range:
Function:
[-200% - 200%]
This is a read out parameter only.
Shows the actual torque yielded in percentage of the rated tor-
que, based on the setting of the motor size and rated speed in
Motor Power [kW]
, par. 1-20 or
Motor Power [Hp]
, par. 1-21
and
Motor Nominal Speed
, par. 1-25.
This is the value monitored by the
Broken Belt Function
set in
par. 22-6*.
2.15.4. 16-3* Drive Status
Parameters for reporting the status of the frequency converter.
16-30 DC Link Voltage
Range:
Function:
0V
*
[0 - 10000 V]
View a measured value. The value is filtered, and thus approx.
30 ms may pass from when an input value changes to when the
data read-out value changes.
VLT
®
AQUA Drive Programming Guide
2. Parameter Description
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
163
2