atile memory, so changed parameter values will be retained at
power-down.
[0]
*
Off
Deactivates the non-volatile storage function.
[1]
Store edit setup
Stores all parameter values in the set-up selected in par. 9-70
in the non-volatile memory. The selection returns to Off [0]
when all values have been stored.
[2]
Store all set-ups
Stores all parameter values for all set-ups in the non-volatile
memory. The selection returns to
Off
[0] when all parameter
values have been stored.
9-72 Drive Reset
Option:
Function:
[0]
*
No action
[1]
Power-on reset
Resets frequency converter upon power-up, as for power-cycle.
[3]
Comm. option reset
Resets the Profibus option only, useful after changing certain
settings in parameter group 9-**, e.g. par. 9-18.
When reset, the frequency converter disappears from the field-
bus, which may cause a communication error from the master.
9-80 Defined Parameters (1)
Array [116]
No LCP access
Read only
0
*
[0 - 115]
This parameter displays a list of all the defined frequency con-
verter parameters available for Profibus.
9-81 Defined Parameters (2)
Array [116]
No LCP access
Read only
0
*
[0 - 115]
This parameter displays a list of all the defined frequency con-
verter parameters available for Profibus.
9-82 Defined Parameters (3)
Array [116]
No LCP access
VLT
®
AQUA Drive Programming Guide
2. Parameter Description
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
123