2.17. Main Menu - FC Closed Loop - Group 20
2.17.1. Drive Closed Loop, 20-**
This parameter group is used for configuring the closed loop PID Controller, that controls the
output frequency of the frequency converter.
2.17.2. Feedback, 20-0*
This parameter group is used to configure the feedback signal for the frequency converter’s closed
loop PID Controller. Whether the frequency converter is in Closed Loop Mode or Open Loop Mode,
the feedback signals can be shown on the frequency converter’s display. It can also be used to
control a frequency converter analog output, and be transmitted over various serial communica-
tion protocols.
20-00 Feedback 1 Source
Option:
Function:
[0]
No Function
[1]
Analog Input 53
[2]
*
Analog Input 54
[3]
Pulse Input 29
[4]
Pulse Input 33
[7]
Analog Input X30/11
[8]
Analog Input X30/12
[9]
Analog Input X42/1
[10]
Analog Input X42/3
[100]
Bus Feedback 1
[101]
Bus Feedback 2
[102]
Bus Feedback 3
Up to three different feedback signals can be used to provide
the feedback signal for the frequency converter’s PID Controller.
2. Parameter Description
VLT
®
AQUA Drive Programming Guide
174