[16-96 ] Prev.
Maintenance
Word
9-27 Parameter Edit
Option:
Function:
Parameters can be edited via Profibus, the standard RS485 in-
terface, or the LCP.
[0]
Disabled
Disables editing via Profibus.
[1]
*
Enabled
Enables editing via Profibus.
9-28 Process Control
Option:
Function:
Process control (setting of Control Word, speed reference, and
process data) is possible via either Profibus or standard fieldbus
but not both simultaneously. Local control is always possible via
the LCP. Control via process control is possible via either termi-
nals or fieldbus depending on the settings in par. 8-50 to 8-56.
[0]
Disable
Disables process control via Profibus, and enables process con-
trol via standard fieldbus or Profibus Master class 2.
[1]
*
Enable cyclic master
Enables process control via Profibus Master Class 1, and disables
process control via standard fieldbus or Profibus Master class 2.
9-53 Profibus Warning Word
Option:
Function:
This parameter displays Profibus communication warnings.
Please refer to the
Profibus Operating Instructions
for further
information.
Read only
Bit:
Meaning:
0
Connection with DP-master is not
1
Not used
2
FDL (Field-bus Data link Layer) is not ok
3
Clear data command received
4
Actual value is not updated
5
Baudrate search
6
PROFIBUS ASIC is not transmitting
7
Initializing of PROFIBUS is not ok
8
Drive is tripped
9
Internal CAN error
10
Wrong configuration data from PLC
11
Wrong ID sent by PLC
12
Internal error occured
13
Not configured
14
Timeout active
15
Warning 34 active
9-63 Actual Baud Rate
Option:
Function:
This parameter displays the actual Profibus baud rate. The Pro-
fibus Master automatically sets the baud rate.
VLT
®
AQUA Drive Programming Guide
2. Parameter Description
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark