6-52 Terminal 42 Output Max Scale
Range:
Function:
100%
*
[0.00 – 200%]
Scale the maximum output of the selected analog signal at ter-
minal 42. Set the value to the maximum value of the current
signal output. Scale the output to give a current lower than 20
mA at full scale; or 20 mA at an output below 100% of the
maximum signal value. If 20 mA is the desired output current
at a value between 0 - 100% of the full-scale output, pro-
gramme the percentage value in the parameter, i.e. 50% = 20
mA. If a current between 4 and 20 mA is desired at maximum
output (100%), calculate the percentage value as follows:
20
m A/ desired maximum current × 100 %
i.e. 10mA : 20 mA
10
mA × 100 % = 200 %
6-53 Terminal 42 Output Bus Control
Range:
Function:
0.00%
*
[0.00 – 100.00 %]
Holds the level of Output 42 if controlled by bus.
6-54 Terminal 42 Output Timeout Preset
Range:
Function:
0.00%
*
[0.00 – 100.00 %]
Holds the preset level of Output 42.
In case of a bus timeout and a timeout function is selected in
par. 6-50 the output will preset to this level.
2. Parameter Description
VLT
®
AQUA Drive Programming Guide
104
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
2