[33]
Set digital output B
low
Any output with ‘digital output 2’ selected is low (off).
[34]
Set digital output C
low
Any output with ‘digital output 3’ selected is low (off).
[35]
Set digital output D
low
Any output with ‘digital output 4’ selected is low (off).
[36]
Set digital output E
low
Any output with ‘digital output 5’ selected is low (off).
[37]
Set digital output F
low
Any output with ‘digital output 6’ selected is low (off).
[38]
Set digital output A
high
Any output with ‘digital output 1’ selected is high (closed).
[39]
Set digital output B
high
Any output with ‘digital output 2’ selected is high (closed).
[40]
Set digital output C
high
Any output with ‘digital output 3’ selected is high (closed).
[41]
Set digital output D
high
Any output with ‘digital output 4’ selected is high (closed).
[42]
Set digital output E
high
Any output with ‘digital output 5’ selected is high (closed).
[43]
Set digital output F
high
Any output with ‘digital output 6’ selected is high (closed).
[60]
Reset Counter A
Resets Counter A to zero.
[61]
Reset Counter B
Resets Counter A to zero.
[70]
Start Timer 3
Starts timer 3, see par. 13-20 for further description.
[71]
Start Timer 4
Starts timer 4, see par. 13-20 for further description.
[72]
Start Timer 5
Starts timer 5, see par. 13-20 for further description.
[73]
Start Timer 6
Starts timer 6, see par. 13-20 for further description.
[74]
Start Timer 7
Starts timer 7, see par. 13-20 for further description.
2.13. Main Menu - Special Functions -Group 14
2.13.1. 14-** Special Functions
Parameter group for configuring special frequency converter functions.
2.13.2. Inverter Switching, 14-0*
Parameters for configuring the inverter switching.
14-00 Switching Pattern
Option:
Function:
[0]
*
60 AVM
[1]
SFAVM
Select the switching pattern: 60° AVM or SFAVM.
VLT
®
AQUA Drive Programming Guide
2. Parameter Description
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
143
2