38 | © Danfoss | August 2018
AQ00000211
ENGINEERING TOMORROW
Important
There is no validation in the PVED-CLS that P3074: Cut-off valve CL pull current > P3076: Cut-off valve CL hold
current.
Important
Danfoss recommends not to change the default values for P3074, P3076 and P3097.
Contact your local technical support at Danfoss Power Solutions if there is a need to change these parameters.
Name
A
ddr
es
s
D
at
a t
yp
e
U
ni
t
Description of parameter
U
se
r
Range
D
a
nf
o
ss
de
fa
ul
t
val
u
e
S
a
fet
y
cri
ti
ca
l
p
a
ra
m
et
ers
‘
S
’
Mi
n
.
M
ax.
Cut-off valve present
P3072
U8
-
Cut-off Valve Present/Not Present
Valid Values: 0 (NOT PRESENT); 255 (PRESENT)
OEM
0
255
255
S
Cut-off valve control
mode
P3073
U8
-
Cut-off Valve control mode Close loop Control or ON-OFF control
Valid Values: 0 (ON-OFF control); 255 (Closed loop control)
OEM
0
255
255
S
Cut-off valve CL pull
current
P3074
U16
mAmp
Current required to activate Cut-off valve
OEM
100
2000
1100
S
Cut-off valve CL hold
current
P3076
U16
mAmp
Current required to maintain Cut-off in ON state
OEM
100
2000
500
S
Cut-off valve PWM pre-
load value
P3097
U8
%
Cut-off valve PWM pre-load value
OEM
0
100
100
Table 8
7.1.2
Cut-off valve monitoring
The PVED-CLS continuously monitors the cut-off solenoid valve current level and if it exceeds the defined threshold of
2500mA, the PVED-CLS will de-energize the cut-off solenoid valve and enter safe state.
Furthermore, in off-road mode the PVED-CLS will monitor if the cut-off solenoid valve current level drops below half
of the setting of
P3076: Cut-off valve CL hold current
. If the cut-off solenoid valve current is found below this level, the
PVED-CLS will de-energize the cut-off solenoid valve and enter safe state.
Whenever switching from on-road mode to off-road mode, the PVED-CLS is performing diagnostics on the cut-off valve,
this is called off-road safety check. If the off-road safety check is not successfully completed, a change to off-road mode
will not be permitted and thus no electro-hydraulic steering will be available. Two different off-road safety checks can be
executed, depending on the valve type.
7.1.2.1
Cut-off valve monitoring for OSPE, EHi-E
This safety check will be executed if
P3081: Valve type
is set to 0
(OSPE, EHi-E)
and a mode change from on-road
mode to off-road mode is requested.
The PVED-CLS checks that the EH-valve main spool can move to a set-point, inside the mechanical deadband, within
the time specified by
P3078: Cut-off valve monitoring POST timeout
, when it is commanded to do so and the cut-off
solenoid valve is turned on. Then the PVED-CLS checks that the EH-valve main spool cannot move when the cut-off
solenoid valve is turned off, even though the EH-valve main spool is commanded to.
Summary of Contents for PVED-CLS
Page 6: ...6 Danfoss August 2018 AQ00000211 ENGINEERING TOMORROW ...
Page 71: ... Danfoss August 2018 AQ00000211 71 ENGINEERING TOMORROW Figure 29 ...
Page 127: ... Danfoss August 2018 AQ00000211 127 ENGINEERING TOMORROW ...
Page 147: ... Danfoss August 2018 AQ00000211 147 ENGINEERING TOMORROW ...
Page 182: ...182 Danfoss August 2018 AQ00000211 ENGINEERING TOMORROW ...