Installation Guide
ECL Comfort 210 / 310, application A214 / A314
2.5.2 Electrical connections, 230 V a.c., power supply, pumps, dampers, motorized control valves etc.
Connections, in general.
See also the Mounting Guide (delivered with the application key) for application specific connections.
Terminals
Max. load
ECL 210
ECL 310
19
18
4 (2) A / 230 V a.c. *
17
4 (2) A / 230 V a.c. *
16
16
15
15
4 (2) A / 230 V a.c. *
14
14
13
13
4 (2) A / 230 V a.c. *
12
12
4 (2) A / 230 V a.c. *
11
11
4 (2) A / 230 V a.c. *
10
10
230 V a.c., Neutral (N)
9
9
230 V a.c., Live (L)
8
8
7
7
0,2 A / 230 V a.c.
6
6
0,2 A / 230 V a.c.
5
5
4
4
0,2 A / 230 V a.c.
3
3
0,2 A / 230 V a.c.
2
0,2 A / 230 V a.c.
1
0,2 A / 230 V a.c.
* 4 A for ohmic load, 2 A for inductive load
Factory established jumpers in the base part:
5 to 8, 9 to 14, L to 5 and L to 9, N to 10
Danfoss District Energy
VI.GU.A2.02
DEN-SMT/DK