Installation Guide
ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Application
S4 filter
1x304
Circuit
Setting range
Factory setting
All
*
*
The filtering of the measured temperature at S4 prevents instability in the
control of the duct temperature.
The set value is an indirect time constant. The resulting time constant is
listed in the examples below.
* See Appendix “Parameter ID overview”
Low value:
Low filtering (minor dampening)
High value:
High filtering (major dampening)
The setting values (examples) give the following approximate time
constants:
Set value (examples):
Resulting time constant:
1
1 sec
2
1.5 sec
5
4 sec
10
7 sec
20
14 sec
50
35 sec
100
70 sec
MENU > Settings > Application
MENU > Settings > Control par. 2
1. step level
1x368
Circuit
Setting range
Factory setting
All
*
*
The total control range is covered by M2 within the set % value.
* See Appendix “Parameter ID overview”
MENU > Settings > Application
MENU > Settings > Control par. 2
2. step level
1x369
Circuit
Setting range
Factory setting
All
*
*
From the set % value and up to 100 %, the control is covered by M1.
* See Appendix “Parameter ID overview”